| 2018-03-09 11:05:56 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. DUE TO INCREASE IN VALUE OF WORK, A NOTICE OF |
| | COMMENCEMENT WILL BE REQUIRED. PROVIDE TO PERMIT |
| | SPECIALIST AT RESUBMITTAL. FS 713.13 |
| | 2. VALUE LISTED FOR THE ADDITIONAL WORK SHOWN ON PLAN |
| | APPEARS LOW. PROVIDE COPY OF SIGNED CONTRACT FOR |
| | ADDITIONAL WORK TO INCLUDE SCOPE AND VALUE OF WORK |
| | INCLUDING MATERIALS AND LABOR. FBC 109.3 |
| | 3. PROVIDE TWO COPIES OF PLAN WITH SIGNATURE OF PERSON |
| | RESPONSIBLE FOR DESIGN ON EACH PLAN. A PHOTOCOPIED |
| | SIGNATURE IS NOT ACCEPTABLE. FBC 107.1; FS 471.025, |
| | 471.003, 481.229 |
| | 4. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| | WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC RE |
| | E3706.2, E3902 |
| | 5. PROVIDE AFCI PROTECTION PER CODE: ?BRANCH CIRCUITS |
| | THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE |
| | OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS, DINING |
| | ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, |
| | BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, |
| | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS |
| | SHALL BE AFCI PROTECTED.? A NOTE WILL SUFFICE. NEC |
| | 210.12; FBC RE E3902.16 |
| | 6. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| | FBC EC R404.1 |
| | 7. RECEPTACLES IN KITCHEN REQUIRE GFCI PROTECTION. |
| | PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.6 |
| | 8. PROVIDE GFCI PROTECTION FOR DISHWASHER IF |
| | APPLICABLE. NEC 210.8(D); FBC RE E3902.10 |
| | 9. IT APPEARS THE LOCATION OF THE NEW PANEL ON ORIGINAL |
| | PLAN IS LOCATED IN THE KITCHEN. BE ADVISED THAT |
| | CONDUCTORS FROM METER CAN TO FIRST MEANS OF DISCONNECT |
| | ARE NOT PERMITTED TO EXTEND FARTHER THAN 8 FEET FROM |
| | THE METER WITHOUT OVERCURRENT PROTECTION. IF THE FEED |
| | IS UNDERGROUND AS SHOWN ON THE ORIGINAL PLAN, THIS |
| | WOULD BE ACCEPTABLE. HOWEVER, IF THE FEED MUST RUN |
| | THROUGH THE STRUCTURE, A MAIN DISCONNECT WILL BE |
| | REQUIRED ON THE EXTERIOR OF THE HOUSE. CLARIFY AND/OR |
| | CORRECT. NEC 230.70; FBC RE E3601.6 |
| | 10. PROVIDE SMOKE ALARMS IN EACH LOCATION REQUIRED PER |
| | CODE. SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE |
| | EXISTING OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC |
| | R314.3, FBC 107.2.1 |
| | 11. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A |
| | NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14 |
| | 12. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING |
| | REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE |
| | INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG |
| | THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET |
| | FROM A RECEPTACLE OUTLET, EXCEPT FOR KITCHENS WHICH |
| | REQUIRE THAT RECEPTACLE OUTLETS SHALL BE INSTALLED SO |
| | THAT NO POINT ALONG THE WALL LINE IS MORE THAN 24 |
| | INCHES MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET |
| | IN THAT SPACE. A MINIMUM OF TWO 20 AMP CIRCUITS ARE |
| | REQUIRED FOR COUNTER OUTLETS IN KITCHEN. PROVIDE |
| | CORRECTIONS. NEC 210.11, 210.52; FBC RE E3901.2.1, |
| | E3901.4 |
| | 13. A GFCI PROTECTED OUTLET ON A 20 AMP CIRCUIT IS |
| | REQUIRED WITHIN 3 FEET OF EACH BASIN. PROVIDE |
| | CORRECTION. NEC 210.11(C)(3), 210.52(D); FBC RE |
| | E3703.4, E3901.6 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |