| 2019-01-08 17:08:04 | 3ND REVIEW: FBC 2017 6TH EDITION |
| | |
| | IT IS UNCLEAR WHAT NEW PLUMBING WORK WAS DONE IN ORDER |
| | TO CLARIFY WHAT WAS DONE I AM REQUESTING A MEETING BE |
| | SCHEDULED SEE CONTACT INFORMATION BELOW, WITHOUT |
| | CLARIFICATION A PERMIT WILL NOT BE APPROVED. |
| | |
| | PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED 3RD |
| | REQUEST |
| | |
| | 1. PROVIDE A CODE COMPLIANT SANITARY ISOMETRIC DRAWING. |
| | PER WPB AMEND TO FBC 107.3.5.1.3 |
| | |
| | 3. PLACE NOTE ON PLAN PIPES MAY NEED TO BE EXPOSED FOR |
| | INSPECTION UP TO THE DISCRETION OF THE FIELD INSPECTOR. |
| | PER FBC PL 312 |
| | |
| | PREVIOUS COMMENTS 2ND REQUEST |
| | |
| | 1. THE LAVATORY,S NOT NOT APPEAR TO HAVE THE REQUIRED |
| | 21" INFRONT OF FIXTURE PER FBC PL 405.3.1 |
| | |
| | 2. SHT. A.02 THE PIPING FOR THE NEW KITCHEN SHALL NOT |
| | CONNECT TO THE WET VENT OF THE BATHROOM PER FBC PL |
| | 912.1 |
| | |
| | 3. PLEASE INDICATE ON THE PLAN LOCATION OF THE WATER |
| | HEATER AND MARK THE FIXTURE AS NEW OR EXISTING. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |