Text |
| 2018-06-07 08:44:45 | 2ND REVIEW: FBC 2017 5TH EDITION |
| | FBC 2017 EXISTING BUILDING |
| | |
| | UNDER REVIEW |
| | |
| | 5/18/18 MET WITH OWNER, EXPLAINED FIRST REVIEW COMMENTS |
| | OF 4/18/18 WERE NOT SUFFIENTLY ADDRESSED. |
| | |
| | FIRST REVIEW COMMENTS SEE BELOW: |
| | |
| | AS DISCUSSED WITH ARCHITECT NORM PAUL, I PROVIDED VIA |
| | EMAIL THE FILE RECORD REGARDING THE BUILDING AT THE |
| | SUBJECT ADDRESS. IT ESTABLISHES THAT THE SINGLE STORY |
| | PORTION SHOWN AS A THIRD UNIT ON THE PROPERTY WAS ONLY |
| | A ROOM WITH A BATHROOM AND A ONE CAR GARAGE IN 1964. |
| | THERE IS NO PERMIT RECORD ON FILE THAT I CAN FIND TO |
| | CHANGE THAT AREA OF APPROXIMATELY 605 SF FROM A ROOM |
| | WITH BATH AND GARAGE TO A DWELLING UNIT. THERE ARE |
| | RECORDS FOR OTHER WORK SUCH AS RECENT WINDOW, ROOFING |
| | AND ELECTRICAL UPGRADES. THE WINDOW SERVING THE BEDROOM |
| | MAY NOT MEET EGRESS REQUIREMENTS. SUCH PERMITS ISSUED |
| | SEPARATELY DO NOT ALLOW FOR THE LEGAL ESTABLISHMENT OF |
| | A THIRD UNIT. THE UNIT MAY APPEAR LEGAL BUT AGAIN, THE |
| | RECORD TO LEGALLY ESTABLISH IT IS NOT APPARENT. THE |
| | PRESUMPTION IS THAT WORK WAS DONE IN THE PAST WITHOUT |
| | ALL THE REQUIRED PERMITTING TO PROPERLY AND LEGALLY |
| | ESTABLISH THE USE OF THE APPARENT THIRD UNIT. I |
| | PROVIDED THE CONTACT INFORMATION TO THE CUSTOMER FOR |
| | CRAIG MCPHERSON, CUSTOMER SERVICE ASSOCIATE IN THE |
| | EVENT THEY MAY WISH TO REQUEST HE CHECK RECORDS TO |
| | VERIFY MY CONCLUSION. TO PROCEED WITH LEGALLY |
| | ESTABLISHING THE THIRD UNIT, THE APPLICANT MUST NOW |
| | DEVELOP A PLAN TO DEMONSTRATE COMPLIANCE WITH CURRENT |
| | APPLICABLE CODE AS IF CHANGING THE LAYOUT ON FILE TO A |
| | LEGAL DWELLING UNIT UNDER THE REQUIREMENTS OF THE FBC |
| | 2017 EXISTING BUILDING CHAPTER 10 CHANGE OF OCCUPANCY. |
| | THE PLAN MUST SHOW COMPLIANCE WITH PLUMBING REGARDING |
| | THE CONNECTIONS TO THE KITCHEN AS THE BATHROOM IS |
| | PRESUMED TO BE EXISTING, COMPLETE ELECTRICAL COMPLIANCE |
| | FOR THE INTERIOR IN TERMS OF REQUIRED ELECTRICAL |
| | CIRCUITS, DEVICES AND SMOKE ALARMS, ETC, A MECHANICAL |
| | PLAN FOR REQUIRED HEAT AND ANY PROVIDED COOLING, AND AN |
| | ENERGY SUBMITTAL. ADDITIONALLY COMPLIANCE WITH CHAPTER |
| | 9 FBC IS REQUIRED AS TO FIRE PROTECTION SYSTEMS |
| | INCLUDING INCLUDING FIRE SPRINKLER AND FIRE ALARM. THE |
| | ARCHITECTURAL PLAN MUST PROVIDE THE CODE REFERENCE AND |
| | A SCOPE OF WORK DISCUSSING THE ATTEMPT TO LEGALIZE |
| | EXISTING WORK THROUGH ASSURING THE RECONFIGURATION OF |
| | THE SPACE COMPLIES WITH THE AFOREMENTIONED FBC 2017 |
| | EXISTING BUILDING CHAPTER 10 CHANGE OF OCCUPANCY. PRIOR |
| | TO PERMIT ISSUANCE THE APPROVED PLAN WILL NEED TO BE |
| | REVIEWED BY THE PBC IMPACT FEE OFFICE AND A FEE MAY BE |
| | DUE TO THEM. AN APPROPRIATE VALE FOR THIS WORK WILL |
| | NEED TO BE ESTABLISHED. $1,200.00 SEEMS LOW. IF ANY NEW |
| | WORK IS TO BE DONE, SEPARATE PERMITS PER TRADE WILL BE |
| | REQUIRED. |
| | |
| | THE SUBMITTED PLAN IS DEFICIENT AND DOES NOT MEET THE |
| | MINIMUM PLAN REVIEW CRITERIA REQUIRED IN FBC 107 AND |
| | THE ITEMS LISTED GENERALLY ABOVE. A COMPLETE REIVEW |
| | CANNOT BE CONDUCTED. PLEASE NOTE THAT ANY REVIEWS |
| | COMPLETED PRIOR TO THIS DATE AND APPROVED ARE SUBJECT |
| | TO CHANGE. |
| | |
| | |
| | STEVEN KENNEDY, CBO |
| | ASSISTANT BUILDING OFFICIAL |
| | (561) 805-6710 |
| | [email protected] |
| | |
| | 1ST REVIEW: FBC 2017 5TH EDITION |
| | 1ST REVIEW FBC 2017 EXISTING BUILDING |
| | |
| | |
| | AS DISCUSSED WITH ARCHITECT NORM PAUL, I PROVIDED VIA |
| | EMAIL THE FILE RECORD REGARDING THE BUILDING AT THE |
| | SUBJECT ADDRESS. IT ESTABLISHES THAT THE SINGLE STORY |
| | PORTION SHOWN AS A THIRD UNIT ON THE PROPERTY WAS ONLY |
| | A ROOM WITH A BATHROOM AND A ONE CAR GARAGE IN 1964. |
| | THERE IS NO PERMIT RECORD ON FILE THAT I CAN FIND TO |
| | CHANGE THAT AREA OF APPROXIMATELY 605 SF FROM A ROOM |
| | WITH BATH AND GARAGE TO A DWELLING UNIT. THERE ARE |
| | RECORDS FOR OTHER WORK SUCH AS RECENT WINDOW, ROOFING |
| | AND ELECTRICAL UPGRADES. THE WINDOW SERVING THE BEDROOM |
| | MAY NOT MEET EGRESS REQUIREMENTS. SUCH PERMITS ISSUED |
| | SEPARATELY DO NOT ALLOW FOR THE LEGAL ESTABLISHMENT OF |
| | A THIRD UNIT. THE UNIT MAY APPEAR LEGAL BUT AGAIN, THE |
| | RECORD TO LEGALLY ESTABLISH IT IS NOT APPARENT. THE |
| | PRESUMPTION IS THAT WORK WAS DONE IN THE PAST WITHOUT |
| | ALL THE REQUIRED PERMITTING TO PROPERLY AND LEGALLY |
| | ESTABLISH THE USE OF THE APPARENT THIRD UNIT. I |
| | PROVIDED THE CONTACT INFORMATION TO THE CUSTOMER FOR |
| | CRAIG MCPHERSON, CUSTOMER SERVICE ASSOCIATE IN THE |
| | EVENT THEY MAY WISH TO REQUEST HE CHECK RECORDS TO |
| | VERIFY MY CONCLUSION. TO PROCEED WITH LEGALLY |
| | ESTABLISHING THE THIRD UNIT, THE APPLICANT MUST NOW |
| | DEVELOP A PLAN TO DEMONSTRATE COMPLIANCE WITH CURRENT |
| | APPLICABLE CODE AS IF CHANGING THE LAYOUT ON FILE TO A |
| | LEGAL DWELLING UNIT UNDER THE REQUIREMENTS OF THE FBC |
| | 2017 EXISTING BUILDING CHAPTER 10 CHANGE OF OCCUPANCY. |
| | THE PLAN MUST SHOW COMPLIANCE WITH PLUMBING REGARDING |
| | THE CONNECTIONS TO THE KITCHEN AS THE BATHROOM IS |
| | PRESUMED TO BE EXISTING, COMPLETE ELECTRICAL COMPLIANCE |
| | FOR THE INTERIOR IN TERMS OF REQUIRED ELECTRICAL |
| | CIRCUITS, DEVICES AND SMOKE ALARMS, ETC, A MECHANICAL |
| | PLAN FOR REQUIRED HEAT AND ANY PROVIDED COOLING, AND AN |
| | ENERGY SUBMITTAL. ADDITIONALLY COMPLIANCE WITH CHAPTER |
| | 9 FBC IS REQUIRED AS TO FIRE PROTECTION SYSTEMS |
| | INCLUDING INCLUDING FIRE SPRINKLER AND FIRE ALARM. THE |
| | ARCHITECTURAL PLAN MUST PROVIDE THE CODE REFERENCE AND |
| | A SCOPE OF WORK DISCUSSING THE ATTEMPT TO LEGALIZE |
| | EXISTING WORK THROUGH ASSURING THE RECONFIGURATION OF |
| | THE SPACE COMPLIES WITH THE AFOREMENTIONED FBC 2017 |
| | EXISTING BUILDING CHAPTER 10 CHANGE OF OCCUPANCY. PRIOR |
| | TO PERMIT ISSUANCE THE APPROVED PLAN WILL NEED TO BE |
| | REVIEWED BY THE PBC IMPACT FEE OFFICE AND A FEE MAY BE |
| | DUE TO THEM. AN APPROPRIATE VALE FOR THIS WORK WILL |
| | NEED TO BE ESTABLISHED. $1,200.00 SEEMS LOW. IF ANY NEW |
| | WORK IS TO BE DONE, SEPARATE PERMITS PER TRADE WILL BE |
| | REQUIRED. |
| | |
| | THE SUBMITTED PLAN IS DEFICIENT AND DOES NOT MEET THE |
| | MINIMUM PLAN REVIEW CRITERIA REQUIRED IN FBC 107 AND |
| | THE ITEMS LISTED GENERALLY ABOVE. A COMPLETE REIVEW |
| | CANNOT BE CONDUCTED. PLEASE NOTE THAT ANY REVIEWS |
| | COMPLETED PRIOR TO THIS DATE AND APPROVED ARE SUBJECT |
| | TO CHANGE. |
| | |
| | |
| | STEVEN KENNEDY, CBO |
| | ASSISTANT BUILDING OFFICIAL |
| | (561) 805-6710 |
| | [email protected] |
| | |