| Plan Review Notes For Permit 18030102 |
| Permit Number |
18030102 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-04-20 07:16:35 | 04/20/2018 2ND PLUMBING REVIEW**DEINED** | | | | | | 1) LAV SINK ON 1ST FLOOR SHOWING ON SANITARY RISER | | | ISOMETRIC SHALL NOT CONNECT INTO THE STACK THAT | | | RECEIVESDISCHARGE FROM A TOILET. FBC-R P 3109.2 LAV | | | SINK DOES NOT SHOW ON FLOOR PLAN. | | | | | | 2) 2ND FLOOR GUEST BATHRROM ONLY 1 WET VENTED FIXTURE | | | IS PERMITTED BEYOND THE VENT. FBC-R P3108.2.1 | | | | | | | | | TIM HUNT | | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | 561-805-6695 | | | [email protected] | | | |
|