| 2018-03-12 15:26:29 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PLAN SHOWS A CARBON MONOXIDE ALARM ON SECOND FLOOR |
| | IN HALLWAY. IN ADDITION TO THE CO ALARM, A SMOKE ALARM |
| | IS REQUIRED IN THIS LOCATION. ADDITIONALLY, THE |
| | DOWNSTAIRS BEDROOM SHOULD HAVE A SMOKE ALARM INSIDE THE |
| | BEDROOM AS WELL AS A SMOKE/CO ALARM WITHIN 10 FEET OF |
| | THE BEDROOM, PROVIDE CORRECTION. FBC RE R314.3, R315.1 |
| | 2. PLAN SHOWS A MAIN DISCONNECT ON THE OUTSIDE OF A |
| | HOME, FEEDING AN INTERIOR PANEL. THE CONDUCTORS TO |
| | INTERIOR PANEL SHOULD INCLUDE AN EQUIPMENT GROUNDING |
| | CONDUCTOR. PROVIDE CORRECTION. NEC 250.122; FBC RE |
| | E3704.6, 3607.3.1 |
| | 3. PLAN SHOWS A STANDARD RECESS LIGHT OVER MASTER TUB. |
| | LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE SUITABLE |
| | FOR DAMP LOCATIONS. PROVIDE CORRECTION. NEC 410.10(D); |
| | FBC RE E4003.11 |
| | 4. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL |
| | LOADS. SECOND A/C SYSTEM IS NOT INCLUDED. DEMAND |
| | FACTORS ARE NOT APPLIED PROPERLY. SUB-PANEL LOAD IS |
| | SHOWN AS 12.0 KW IN MAIN PANEL, BUT AS 4.5 KW IN |
| | SUB-PANEL. CLARIFY AND/OR CORRECT. SEE FBC RE FOR |
| | FORMAT. NEC 220; FBC RE E3602.2 |
| | 5. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE |
| | PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH |
| | CIRCUITS SHALL HAVE NO OTHER OUTLETS. PROVIDE |
| | CORRECTION. NEC 210.11(C)(3) , FBC RE E3703.4 |
| | 6. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10 |
| | 7. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, |
| | DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD |
| | SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND |
| | SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN |
| | THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE |
| | INDICATING THE REQUIRED SEPARATE PERMITS AND DATA |
| | SPECIFICATION SHEET SUBMITTALS FOR ANY OF THESE SYSTEMS |
| | PRESENT. FBC 105.1, 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |
| | |