| 2018-03-21 17:42:16 | RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017). |
| | |
| | 1- CLEARLY SPECIFY ALL STRUCTURAL L CONNECTORS FOR ALL |
| | NEW (2)2X12 STRUCTURAL HEADERS AND 4X4 POSTS SHOWN ON |
| | SHEET 1.1. ALSO, SPECIFY POSTS CONNECTIONS AT BOTTOM TO |
| | SHOW COMPLIANCE WITH THE LOAD PATH OF SEC. R601.2 |
| | FBC-RESIDENTIAL. |
| | |
| | R601.2 REQUIREMENTS. |
| | WALL CONSTRUCTION SHALL BE CAPABLE OF ACCOMMODATING ALL |
| | LOADS IMPOSED IN ACCORDANCE WITH SECTION R301 AND OF |
| | TRANSMITTING THE RESULTING LOADS TO THE SUPPORTING |
| | STRUCTURAL ELEMENTS. |
| | |
| | 2- IT LOOKS LIKE THIS BUILDINGS LOCATED IN EXPOSURE "D" |
| | NOT "C" AS SPECIFIED ON DESIGN PARAMETERS ON SHEET 1.1. |
| | REVISE AS REQUIRED. |
| | |
| | R301.2.1.4.3 EXPOSURE CATEGORIES. |
| | AN EXPOSURE CATEGORY SHALL BE DETERMINED IN ACCORDANCE |
| | WITH THE FOLLOWING: |
| | EXPOSURE D. EXPOSURE D SHALL APPLY WHERE THE GROUND |
| | SURFACE ROUGHNESS, AS DEFINED BY SURFACE ROUGHNESS D, |
| | PREVAILS IN THE UPWIND DIRECTION FOR A DISTANCE OF AT |
| | LEAST 5,000 FEET (1524 M) OR 20 TIMES THE HEIGHT OF THE |
| | BUILDING, WHICHEVER IS GREATER. EXPOSURE D SHALL ALSO |
| | APPLY WHERE THE GROUND SURFACE ROUGHNESS IMMEDIATELY |
| | UPWIND OF THE SITE IS B OR C, AND THE SITE IS WITHIN A |
| | DISTANCE OF 600 FEET (183 M) OR 20 TIMES THE BUILDING |
| | HEIGHT, WHICHEVER IS GREATER, FROM AN EXPOSURE D |
| | CONDITION AS DEFINED IN THE PREVIOUS SENTENCE. |
| | |
| | |