2018-03-21 17:42:16RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017).
  
 1- CLEARLY SPECIFY ALL STRUCTURAL L CONNECTORS FOR ALL
 NEW (2)2X12 STRUCTURAL HEADERS AND 4X4 POSTS SHOWN ON
 SHEET 1.1. ALSO, SPECIFY POSTS CONNECTIONS AT BOTTOM TO
 SHOW COMPLIANCE WITH THE LOAD PATH OF SEC. R601.2
 FBC-RESIDENTIAL.
  
 R601.2 REQUIREMENTS.
 WALL CONSTRUCTION SHALL BE CAPABLE OF ACCOMMODATING ALL
 LOADS IMPOSED IN ACCORDANCE WITH SECTION R301 AND OF
 TRANSMITTING THE RESULTING LOADS TO THE SUPPORTING
 STRUCTURAL ELEMENTS.
  
 2- IT LOOKS LIKE THIS BUILDINGS LOCATED IN EXPOSURE "D"
 NOT "C" AS SPECIFIED ON DESIGN PARAMETERS ON SHEET 1.1.
 REVISE AS REQUIRED.
  
 R301.2.1.4.3 EXPOSURE CATEGORIES.
 AN EXPOSURE CATEGORY SHALL BE DETERMINED IN ACCORDANCE
 WITH THE FOLLOWING:
 EXPOSURE D. EXPOSURE D SHALL APPLY WHERE THE GROUND
 SURFACE ROUGHNESS, AS DEFINED BY SURFACE ROUGHNESS D,
 PREVAILS IN THE UPWIND DIRECTION FOR A DISTANCE OF AT
 LEAST 5,000 FEET (1524 M) OR 20 TIMES THE HEIGHT OF THE
 BUILDING, WHICHEVER IS GREATER. EXPOSURE D SHALL ALSO
 APPLY WHERE THE GROUND SURFACE ROUGHNESS IMMEDIATELY
 UPWIND OF THE SITE IS B OR C, AND THE SITE IS WITHIN A
 DISTANCE OF 600 FEET (183 M) OR 20 TIMES THE BUILDING
 HEIGHT, WHICHEVER IS GREATER, FROM AN EXPOSURE D
 CONDITION AS DEFINED IN THE PREVIOUS SENTENCE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  