| 2018-03-19 12:55:31 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET A 1 - THIS PROJECT APPEARS TO BE AN OCCUPANCY |
| | CHANGE. PLEASE INDICATE THE EXISTING OCCUPACNY AND |
| | PROPOSED OCCUPANCY. THE PROPOSED APPEARS TO BE |
| | MERCANTILE |
| | |
| | PER NFPA 101, CHAPTER 6, OCCUPANCY CLASSIFICATION |
| | |
| | 6.1 CLASSIFICATION OF OCCUPANCY. |
| | 6.1.1 GENERAL. |
| | 6.1.1.1 OCCUPANCY CLASSIFICATION. THE OCCUPANCY OF A |
| | BUILDING OR |
| | STRUCTURE, OR PORTION OF A BUILDING OR STRUCTURE, SHALL |
| | BE CLASSIFIED IN |
| | ACCORDANCE WITH 6.1.2 THROUGH 6.1.13. OCCUPANCY |
| | CLASSIFICATION SHALL BE |
| | SUBJECT TO THE RULING OF THE AUTHORITY HAVING |
| | JURISDICTION WHERE THERE IS A |
| | QUESTION OF PROPER CLASSIFICATION IN ANY INDIVIDUAL |
| | CASE. |
| | |
| | PLEASE PROVIDE THE ACCURATE OCCUPANCY. |
| | |
| | |
| | 2) SHEET A 1 - THE INDICATED OCCUPACNY LOAD APPEARS TO |
| | BE LOW AND INCORRECT. |
| | |
| | PER # 1 ABOVE PROVIDE AN ACCURATE OCCUPANCY LOAD PER |
| | NFPA 101. CHAPTER 7, MEANS OF EGRESS |
| | |
| | 7.3.1.2* OCCUPANT LOAD FACTOR. THE OCCUPANT LOAD IN ANY |
| | BUILDING OR PORTION THEREOF SHALL BE NOT LESS THAN THE |
| | NUMBER OF |
| | PERSONS DETERMINED BY DIVIDING THE FLOOR AREA ASSIGNED |
| | TO THAT USE |
| | BY THE OCCUPANT LOAD FACTOR FOR THAT USE AS SPECIFIED |
| | IN TABLE |
| | 7.3.1.2, FIGURE 7.3.1.2 (A), AND FIGURE 7.3.1.2(B). |
| | WHERE BOTH |
| | GROSS AND NET AREA FIGURES ARE GIVEN FOR THE SAME |
| | OCCUPANCY, |
| | CALCULATIONS SHALL BE MADE BY APPLYING THE GROSS AREA |
| | FIGURE TO THE |
| | GROSS AREA OF THE PORTION OF THE BUILDING DEVOTED TO |
| | THE USE FOR |
| | WHICH THE GROSS AREA FIGURE IS SPECIFIED AND BY |
| | APPLYING THE NET |
| | AREA FIGURE TO THE NET AREA OF THE PORTION OF THE |
| | BUILDING DEVOTED TO |
| | THE USE FOR WHICH THE NET AREA FIGURE IS SPECIFIED. |
| | |
| | |
| | |
| | 3) SHEET A 1 - SHELVING AND AISLES ARE INDICATED. THE |
| | TOTAL WIDTH OF THE PROPOSED IS INDICATED A 15'. THERE |
| | ARE THRESS AISLES INDICATED AS 37 1/4" - 37" - 37 1/2" |
| | WHICH LEAVES ABOUT 33" FOR SHELVING. |
| | |
| | THOUGH THE DRAWING IS NOT TO SCALE, IT DOES APPEAR |
| | APPEAR TO BE ENOUGH ROOM FOR THE AMOUNT OF SHELVING. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY. |
| | |
| | |
| | |
| | |
| | 4) SHEET M 1 - THERE IS NO HOOD DUCT WORK INDICATED. |
| | |
| | 36.3.2.3* COMMERCIAL COOKING OPERATIONS. COMMERCIAL |
| | COOKING OPERATIONS SHALL BE PROTECTED IN ACCORDANCE |
| | WITH 9.2.3, |
| | UNLESS THE COOKING EQUIPMENT IS ONE OF THE FOLLOWING |
| | TYPES: |
| | (1) OUTDOOR EQUIPMENT |
| | (2) EQUIPMENT USED ONLY FOR FOOD WARMING |
| | |
| | NFPA 101, CHAPTER 9 |
| | |
| | 9.2.3 COMMERCIAL COOKING OPERATIONS. WHERE REQUIRED BY |
| | ANOTHER |
| | SECTION OF THIS CODE, COMMERCIAL COOKING OPERATIONS |
| | SHALL BE PROTECTED |
| | IN ACCORDANCE WITH NFPA 96, STANDARD FOR VENTILATION |
| | CONTROL AND |
| | FIRE PROTECTION OF COMMERCIAL COOKING OPERATIONS, |
| | UNLESS SUCH |
| | INSTALLATIONS ARE APPROVED EXISTING INSTALLATIONS, |
| | WHICH SHALL BE |
| | PERMITTED TO BE CONTINUED IN SERVICE. |
| | |
| | NFPA 96, |
| | |
| | CHAPTER 4 GENERAL REQUIREMENTS |
| | 4.1 GENERAL. |
| | 4.1.1 COOKING EQUIPMENT USED IN PROCESSES PRODUCING |
| | SMOKE OR GREASE-LADEN VAPORS SHALL BE EQUIPPED WITH AN |
| | EXHAUST |
| | SYSTEM THAT COMPLIES WITH ALL THE EQUIPMENT AND |
| | PERFORMANCE |
| | REQUIREMENTS OF THIS STANDARD. |
| | |
| | PLEASE PRVIDE DUCT DETAILS PER THE REQUIREMENTS. |
| | |
| | |
| | |
| | |
| | 5) A HOOD FIRE SUPPRESSION SYSTEM IS REQUIRED AND SHALL |
| | BE SUBMITTED UNDER SEPARATE PERMIT IN COMPLIANCE WITH |
| | THE APPLICABLE FIRE CODES |
| | |
| | |
| | |
| | 6) SHEET GAS - THERE IS NO INDICATION WITH COMPLAINCE |
| | WITH NFPA CODES. |
| | |
| | 36.5 BUILDING SERVICES. |
| | 36.5.1 UTILITIES. UTILITIES SHALL COMPLY WITH THE |
| | PROVISIONS OF SECTION |
| | 9.1. |
| | |
| | |
| | 9.1 UTILITIES. |
| | 9.1.1 GAS. EQUIPMENT USING GAS AND RELATED GAS PIPING |
| | SHALL BE IN |
| | ACCORDANCE WITH NFPA 54, NATIONAL FUEL GAS CODE, OR |
| | NFPA 58, |
| | LIQUEFIED PETROLEUM GAS CODE, UNLESS SUCH INSTALLATIONS |
| | ARE APPROVED |
| | EXISTING INSTALLATIONS, WHICH SHALL BE PERMITTED TO BE |
| | CONTINUED IN |
| | SERVICE. |
| | |
| | |
| | PLEASE REVIEW TO ENSURE COMPLAINCE AND PROVIDE A |
| | APPLICABLE NOTE OF ACKNOWLEDGEMENT. |
| | |
| | |
| | |
| | |
| | 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |