Plan Review Notes
Plan Review Notes For Permit 18030077
Permit Number 18030077
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2018-03-19 12:55:31THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 1 - THIS PROJECT APPEARS TO BE AN OCCUPANCY
 CHANGE. PLEASE INDICATE THE EXISTING OCCUPACNY AND
 PROPOSED OCCUPANCY. THE PROPOSED APPEARS TO BE
 MERCANTILE
  
 PER NFPA 101, CHAPTER 6, OCCUPANCY CLASSIFICATION
  
 6.1 CLASSIFICATION OF OCCUPANCY.
 6.1.1 GENERAL.
 6.1.1.1 OCCUPANCY CLASSIFICATION. THE OCCUPANCY OF A
 BUILDING OR
 STRUCTURE, OR PORTION OF A BUILDING OR STRUCTURE, SHALL
 BE CLASSIFIED IN
 ACCORDANCE WITH 6.1.2 THROUGH 6.1.13. OCCUPANCY
 CLASSIFICATION SHALL BE
 SUBJECT TO THE RULING OF THE AUTHORITY HAVING
 JURISDICTION WHERE THERE IS A
 QUESTION OF PROPER CLASSIFICATION IN ANY INDIVIDUAL
 CASE.
  
 PLEASE PROVIDE THE ACCURATE OCCUPANCY.
  
  
 2) SHEET A 1 - THE INDICATED OCCUPACNY LOAD APPEARS TO
 BE LOW AND INCORRECT.
  
 PER # 1 ABOVE PROVIDE AN ACCURATE OCCUPANCY LOAD PER
 NFPA 101. CHAPTER 7, MEANS OF EGRESS
  
 7.3.1.2* OCCUPANT LOAD FACTOR. THE OCCUPANT LOAD IN ANY
 BUILDING OR PORTION THEREOF SHALL BE NOT LESS THAN THE
 NUMBER OF
 PERSONS DETERMINED BY DIVIDING THE FLOOR AREA ASSIGNED
 TO THAT USE
 BY THE OCCUPANT LOAD FACTOR FOR THAT USE AS SPECIFIED
 IN TABLE
 7.3.1.2, FIGURE 7.3.1.2 (A), AND FIGURE 7.3.1.2(B).
 WHERE BOTH
 GROSS AND NET AREA FIGURES ARE GIVEN FOR THE SAME
 OCCUPANCY,
 CALCULATIONS SHALL BE MADE BY APPLYING THE GROSS AREA
 FIGURE TO THE
 GROSS AREA OF THE PORTION OF THE BUILDING DEVOTED TO
 THE USE FOR
 WHICH THE GROSS AREA FIGURE IS SPECIFIED AND BY
 APPLYING THE NET
 AREA FIGURE TO THE NET AREA OF THE PORTION OF THE
 BUILDING DEVOTED TO
 THE USE FOR WHICH THE NET AREA FIGURE IS SPECIFIED.
  
  
  
 3) SHEET A 1 - SHELVING AND AISLES ARE INDICATED. THE
 TOTAL WIDTH OF THE PROPOSED IS INDICATED A 15'. THERE
 ARE THRESS AISLES INDICATED AS 37 1/4" - 37" - 37 1/2"
 WHICH LEAVES ABOUT 33" FOR SHELVING.
  
 THOUGH THE DRAWING IS NOT TO SCALE, IT DOES APPEAR
 APPEAR TO BE ENOUGH ROOM FOR THE AMOUNT OF SHELVING.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY.
  
  
  
  
 4) SHEET M 1 - THERE IS NO HOOD DUCT WORK INDICATED.
  
 36.3.2.3* COMMERCIAL COOKING OPERATIONS. COMMERCIAL
 COOKING OPERATIONS SHALL BE PROTECTED IN ACCORDANCE
 WITH 9.2.3,
 UNLESS THE COOKING EQUIPMENT IS ONE OF THE FOLLOWING
 TYPES:
 (1) OUTDOOR EQUIPMENT
 (2) EQUIPMENT USED ONLY FOR FOOD WARMING
  
 NFPA 101, CHAPTER 9
  
 9.2.3 COMMERCIAL COOKING OPERATIONS. WHERE REQUIRED BY
 ANOTHER
 SECTION OF THIS CODE, COMMERCIAL COOKING OPERATIONS
 SHALL BE PROTECTED
 IN ACCORDANCE WITH NFPA 96, STANDARD FOR VENTILATION
 CONTROL AND
 FIRE PROTECTION OF COMMERCIAL COOKING OPERATIONS,
 UNLESS SUCH
 INSTALLATIONS ARE APPROVED EXISTING INSTALLATIONS,
 WHICH SHALL BE
 PERMITTED TO BE CONTINUED IN SERVICE.
  
 NFPA 96,
  
 CHAPTER 4 GENERAL REQUIREMENTS
 4.1 GENERAL.
 4.1.1 COOKING EQUIPMENT USED IN PROCESSES PRODUCING
 SMOKE OR GREASE-LADEN VAPORS SHALL BE EQUIPPED WITH AN
 EXHAUST
 SYSTEM THAT COMPLIES WITH ALL THE EQUIPMENT AND
 PERFORMANCE
 REQUIREMENTS OF THIS STANDARD.
  
 PLEASE PRVIDE DUCT DETAILS PER THE REQUIREMENTS.
  
  
  
  
 5) A HOOD FIRE SUPPRESSION SYSTEM IS REQUIRED AND SHALL
 BE SUBMITTED UNDER SEPARATE PERMIT IN COMPLIANCE WITH
 THE APPLICABLE FIRE CODES
  
  
  
 6) SHEET GAS - THERE IS NO INDICATION WITH COMPLAINCE
 WITH NFPA CODES.
  
 36.5 BUILDING SERVICES.
 36.5.1 UTILITIES. UTILITIES SHALL COMPLY WITH THE
 PROVISIONS OF SECTION
 9.1.
  
  
 9.1 UTILITIES.
 9.1.1 GAS. EQUIPMENT USING GAS AND RELATED GAS PIPING
 SHALL BE IN
 ACCORDANCE WITH NFPA 54, NATIONAL FUEL GAS CODE, OR
 NFPA 58,
 LIQUEFIED PETROLEUM GAS CODE, UNLESS SUCH INSTALLATIONS
 ARE APPROVED
 EXISTING INSTALLATIONS, WHICH SHALL BE PERMITTED TO BE
 CONTINUED IN
 SERVICE.
  
  
 PLEASE REVIEW TO ENSURE COMPLAINCE AND PROVIDE A
 APPLICABLE NOTE OF ACKNOWLEDGEMENT.
  
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  