| 2018-04-04 14:29:17 | 04/04/2018 2ND GAS REVIEW**DENIED** WITH COMMENTS NOTE |
| | |
| | A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS TIME |
| | AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED |
| | UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1) SECOND NOTICE, THE PRINTED INFORMATION ON THE SURVEY |
| | FOR THE GAS IS SO SMALL IT CAN BARELY BE READ. SUBMIT |
| | THE SURVEY WITH NOTES THAT CAN BE READ. WPB AMEND. TO |
| | FBC SEC. 107.2.1. |
| | 2) SECOND NOTICE, THE SIZING TABLE COPIES FOR THE |
| | SCHEDULE 40 METALLIC PIPE AND PE PIPE ARE BARELY |
| | LEGIBLE. SUBMIT TWO CLEAR AND LEGIBLE COPIES OF THESE |
| | SIZING TABLES. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 3) SECOND NOTICE, THE SIZING TABLE YOU SUBMITTED FOR |
| | THE SCHEDULE 40 METALLIC PIPE HAS A MINIMUM LENGTH OF |
| | 10 FEET FOR A SIZING DISTANCE. THE MAXIMUM BTU LOAD FOR |
| | A 3/4 INCH LINE AT 10 FEET IS 360,000 BTU'S AND YOU ARE |
| | SHOWING THE GENERATOR AS 480,000 BTU'S SO THE MINIMUM |
| | SIZE PIPE ON THE LOW PRESSURE SIDE TO THE GENERATOR |
| | SHALL BE 1 INCH. |
| | 4) SECOND NOTICE, SUBMIT PAGES 40 & 41 OF THE |
| | MANUFACTURES SPECS FOR THE REGULATORS. THESE SHEETS |
| | DETAIL THE INSTALLATION METHOD FOR THE REGULATORS. WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 5) SECOND NOTICE, THERE IS AN EXPIRED GAS PERMIT ON |
| | THIS PROPERTY FROM 2007 ( PERMIT APPLICATION # 07060594 |
| | ) THIS PERMIT WILL HAVE TO BE RENEWED AND RECEIVE A |
| | FINAL GAS INSPECTION. PLEASE DISCUSS THIS WITH THE |
| | CURRENT OWNER OF THE PROPERTY AND I CAN BE CONTACTED |
| | WITH ANY QUESTIONS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING INSPECTOR / |
| | PLUMBING PLAN REVIEW |
| | [email protected] |
| | 561-805-6720 |
| | |
| | |
| | |
| | |
| | |