| Date |
Text |
| 2019-01-02 15:47:45 | MECHANICAL PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 3RD REVIEW |
| | RESULTS: DENIED |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. COMMENT # 2 FROM 2ND REVIEW HAS NOT BEEN ADDRESSED. |
| | PROVIDE EQUIPMENT MAKE AND MODEL ON EQUIPMENT SCHEDULE. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE |
| | DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 2. OWNER/AGENT TO SIGN ENERGY SUBMITTAL FORM R405-2014. |
| | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. |
| | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 |
| | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE |
| | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE |
| | COMPLIANCE BY SECTION 405. |
| | |
| | 3. BUILDER/CONTRACTOR TO SIGN ENERGY PERFORMANCE LEVEL |
| | (EPL) DISPLAY CARD. |
| | R401.3 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD |
| | (MANDATORY). |
| | THE BUILDING OFFICIAL SHALL REQUIRE THAT AN ENERGY |
| | PERFORMANCE LEVEL (EPL) DISPLAY CARD BE COMPLETED AND |
| | CERTIFIED BY THE BUILDER TO BE ACCURATE AND CORRECT |
| | BEFORE FINAL APPROVAL OF THE BUILDING FOR OCCUPANCY. |
| | FLORIDA LAW [SECTION 553.9085, FLORIDA STATUTES)] |
| | REQUIRES THE EPL DISPLAY CARD TO BE INCLUDED AS AN |
| | ADDENDUM TO EACH SALES CONTRACT FOR BOTH PRESOLD AND |
| | NON-PRESOLD RESIDENTIAL BUILDINGS. THE EPL DISPLAY CARD |
| | CONTAINS INFORMATION INDICATING THE ENERGY PERFORMANCE |
| | LEVEL AND EFFICIENCIES OF COMPONENTS INSTALLED IN A |
| | DWELLING UNIT. THE BUILDING OFFICIAL SHALL VERIFY THAT |
| | THE EPL DISPLAY CARD COMPLETED AND SIGNED BY THE |
| | BUILDER ACCURATELY REFLECTS THE PLANS AND |
| | SPECIFICATIONS SUBMITTED TO DEMONSTRATE CODE COMPLIANCE |
| | FOR THE BUILDING. A COPY OF THE EPL DISPLAY CARD CAN BE |
| | FOUND IN APPENDIX C. |
| | |
| | 4. PROVIDE 2ND COPY OF ENERGY SUBMITTAL. |
| | FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF |
| | CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL |
| | INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL |
| | BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT |
| | APPLICATION. |
| | |
| | 5. PROVIDE RETURN AIR IN FRONT LEFT BEDROOM. |
| | M1602.4 BALANCED RETURN AIR |
| | ( BEDROOM) 2017 RESIDENTIAL CODE |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED. |
| | |
| | |
| | |
| | |
| | |