Plan Review Notes
Plan Review Notes For Permit 18030013
Permit Number 18030013
Review Stop B
Sequence Number 2
Notes
Date Text
2018-08-28 08:16:49RESIDENTIAL (R3) ALTERATION, ADDITION SECOND BUILDING
 REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017).
  
 ORIGINAL COMMENT:
 1- ACCORDING TO SEC. R301.2.1.4.3 FBC-RESIDENTIAL THIS
 BUILDING IS LOCATED IN EXPOSURE "C" NOT "B". REVISE AS
 REQUIRED INFORMATION IN PLANS AND REQUIRED AND REVISE
 THE DOORS AND WINDOWS DESIGN PRESSURES ACCORDINGLY.
  
 RESPONSE:
 CLARIFY IF WINDOWS/DOORS DESIGN PRESSURES SHOWN ON
 SHEET ED-101 ARE ULTIMATE OR NOMINAL WIND LOADS. DESIGN
 CRITERIA SPECIFIES "DESIGN METHOD: ASD". NEED THIS TO
 VERIFY DESIGN PRESSURES ON PRODUCT APPROVALS SUBMITTED.
 SEC. R301.2.1.3 FBC-RESIDENTIAL.
  
 ORIGINAL COMMENT:
 2- BEDROOM EGRESS WINDOWS DON'T COMPLY WITH SEC. R310.2
 FBC-RESIDENTIAL. REVISE AS REQUIRED. CLEARLY SPECIFY
 SIZE OF WINDOW THATT COMPLIES. SEE WINDOW PRODUCT
 APPROVAL FOR LISTED SIZES.
  
 RESPONSE:
 WINDOW SIZE SPECIFIED (52"W X 57" H) DOESN'T SEEM TO
 COMPLY WITH THE MIN. CLEAR HEIGHT OF 24". PROVIDE
 MANUFACTURER'S CUT SHEETS SHOWING THAT THE SPECIFIED
 WINDOW PROVIDES THE MIN. CLEAR HEIGHT.
  
 ORIGINAL COMMENT:
 3- SPECIFY ROOF VENTILATION AS REQUIRED BY SEC. R806
 FBC-RESIDENTIAL.
  
 RESPONSE:
 SHEET A200 SHOWS ROOF VENT CALCULATIONS USING 1/300
 RATIO. SEC. R806.2 FBC-RESIDENTIAL REQUIRES A RATIO OF
 1/150. IN ORDER TO USE THE 1/300 RATIO NEED TO SHOW
 COMPLIANCE WITH ONE OF THE EXCEPTIONS OF SEC. R806.2
 FBC-RESIDENTIAL. REVISE AS REQUIRED.
  
 ORIGINAL COMMENT:
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) SINGLE HUNG WINDOWS AS SHOWN ON PLANS.
 NOTE: DESIGN PRESSURES WILL BE REVIEWED ONCE CALCULATED
 DESIGN PRESSURES ON SHEET ED-101 ARE CLARIFIED.
  
 B) WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY MARK
 MULLION SIZE TO VERIFY COMPLIANCE WITH THE CALCULATED
 DESIGN PRESSURES.
 NOTE: SPECIFY SIZE OF MULLION.
 NOTE: DESIGN PRESSURES WILL BE REVIEWED ONCE CALCULATED
 DESIGN PRESSURES ON SHEET ED-101 ARE CLARIFIED.
  
 C) INSWING ENTRY DOOR WITH SIDELITE AS SHOWN ON PLANS.
 FLORIDA PRODUCT APPROVAL FL4904-R8 IS MISSING THE DOORS
 INSTALLATION INSTRUCTIONS. PROVIDE COMPLETE PRODUCT
 APPROVAL.
 NOTE: DESIGN PRESSURES WILL BE REVIEWED ONCE CALCULATED
 DESIGN PRESSURES ON SHEET ED-101 ARE CLARIFIED.
  
 D) ALL OUTSWING FRENCH DOORS AS SHOWN ON PLANS.
 NOTE: DESIGN PRESSURES WILL BE REVIEWED ONCE CALCULATED
 DESIGN PRESSURES ON SHEET ED-101 ARE CLARIFIED.
  
 E) GABLE END VENTS AS SHOWN ON PLANS.
 REPEAT COMMENT. NO SUBMITTED.
 NOTE: DESIGN PRESSURES WILL BE REVIEWED ONCE CALCULATED
 DESIGN PRESSURES ON SHEET ED-101 ARE CLARIFIED.
  
 F) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. NOTE: PROVIDE ONLY THE FLORIDA PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED
 CONNECTOR OR DESIGN PROFESSIONAL TO LIST THE FLORIDA
 PRODUCT APPROVAL NUMBER NEXT TO EACH SPECIFIED
 CONNECTOR.
 REPEAT COMMENT. NO SUBMITTED.
  
 G) STORAGE DOUBLE DOORS AS SHOWN ON PLANS. CLARIFY IS
 USING THE SAME DOORS AS ENTRY AND SIDE DOORS.
 NOTE: DESIGN PRESSURES WILL BE REVIEWED ONCE CALCULATED
 DESIGN PRESSURES ON SHEET ED-101 ARE CLARIFIED.
  
 NEW COMMENTS:
 5- DRAWINGS A100 AND A200 ARE NOT LEGIBLE. THEY ARE TOO
 LIGHT. PROVIDE LEGIBLE DRAWINGS. SEC. 107.2.1.3 CITY
 AMENDMENTS.
  
 6- PROVIDE COMPLETE FRAMING DETAILS FOR THE
 INSTALLATION OF THE (2) DOUBLE DOORS AT THE NEW OUTSIDE
 STORAGE. AND, SHOW HOW THE TWO DOUBLE DOORS ARE MULLED
 TOGETHER.T SEC. R301.1 FBC-RESIDENTIAL.
  
 7- PROVIDE LANDING FOR NEW STAIRS STAIRS AS REQUIRED BY
 SEC. R311.3 AND R311.3.2 FBC.-RESIDENTIAL.
  
 8- EXISTING COTTAGE PROPOSED ELEVATION ON SHEET A200
 DOESN'T MATCH EXISTING FLOOR PLAN ON SHEET ED-101. IT
 IS NOT CLEAR IF DOING WORK ON COTTAGE OR NOT. SEC.
 107.2.1 CITY AMENDMENTS.
  
 9- SHEET S-100:
 A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 VENTILATION OF UNDER FLOOR SPACE FOR THE ADDITION.. SEE
 SEC. R408.1 FBC-RESIDENTIAL FOR REQUIRED LOCATION.
  
 B) ALL EXTERIOR FOOTING NEED TO BE NO LESS THAN 12"
 BELOW GRADE AS REQUIRED BY SEC. R403.1.4
 FBC-RESIDENTIAL. REVISE ALL FOOTING DETAILS AS
 REQUIRED.
  
 10- CROSS SECTION "F" ON SHEET S-102: PROVIDE COMPLETE
 DETAILS AND SPECIFICATIONS FOR CONNECTION OF EXTERIOR
 WALL TO FOUNDATION CLEARLY SHOWING THE LOAD PATH.
 CLEARLY SPECIFY ANCHOR BOLT SIZE. SEC. R401.2
 FBC-RESIDENTIAL.
  
 11- ACCORDING TO SEC. R403.1.2 AND TABLE R403.1.2
 FBC-RESIDENTIAL THE FOOTING SIZE SPECIFIED FOR THE
 ADDITION MAY BE TOO SMALL FOR UPLIFT RESISTANCE. SEE
 TABLE R403.1.2 FOOTING TYPE "F". ENGINEER TO PROVIDE
 ANALYSIS SHOWING THAT SPECIFIED FOOTING SIZE IS
 ADEQUATE. SEC. 107.2.1.2 CITY AMENDMENTS.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DON'T STAPLE OLD DRAWINGS TO PLANS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  