| 2018-03-23 17:33:04 | RESIDENTIAL (R3) ADDITION/ ALTERATION, MECHANICAL |
| | REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017). |
| | |
| | 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS AS |
| | REQUIRED BY SEC. M1401.3 FBC-RESIDENTIAL. |
| | M1401.3 EQUIPMENT AND APPLIANCE SIZING. |
| | HEATING AND COOLING EQUIPMENT AND APPLIANCES SHALL BE |
| | SIZED IN ACCORDANCE WITH ACCA MANUAL S OR OTHER |
| | APPROVED SIZING METHODOLOGIES BASED ON BUILDING LOADS |
| | CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER |
| | APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES. |
| | |
| | 2- PROVIDE COMPLETE EQUIPMENT SPECIFICATIONS ON THE |
| | MECHANICAL PLAN. SEC. 107.5.3(11) CITY AMENDMENTS. |
| | NOTE: COORDINATE WITH ITEM #1 ABOVE. ALSO, COORDINATE |
| | CFM'S SHOWN ON PLAN WITH EQUIPMENT SIZE TO AVOID |
| | CONFLICTS/DELAYS. |
| | |
| | 3- THE RETURN AIR CAN NOT BE TAKEN FROM THE KITCHEN. |
| | REVISE A S REQUIRED. SEC. M1602.2 FBC-RESIDENTIAL. |
| | |
| | 4- MASTER BATHROOM NEEDS ANOTHER EXHAUST FAN. ONLY ONE |
| | SHOWN IN THE WATER CLOSET COMPARTMENT. REVISE AS |
| | REQUIRED. SEC. R303.3 AND SEC. M1507.2 FBC-RESIDENTIAL. |
| | |
| | 5- BEDROOM ADJACENT TO THE MASTER BEDROOM IS MISSING |
| | THE RETURN AIR OPENING FOR BALANCE RETURN AIR AS |
| | REQUIRED BY SEC. M1602.3. REVISE AS REQUIRED. |
| | |
| | 6- ENGINEER OF RECORD TO SIGN AND SEAL DRAWING AS |
| | REQUIRED BY CHAPTER 471 F.S. WHEN SUBMITTING DOCUMENTS |
| | FOR PUBLIC RECORDS. |
| | |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. |
| | |
| | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY |
| | REVIEWED DRAWINGS. DON?T STAPLE OLD DRAWINGS TO PLANS. |
| | |
| | |