Plan Review Notes
Plan Review Notes For Permit 18030013
Permit Number 18030013
Review Stop E
Sequence Number 1
Notes
Date Text
2018-03-27 08:20:16FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 KITCHEN COUINTER DOES NOT APPEAR TO MEET THE
 REQUIREMENTS OF THE CODE FOR SPACING
  
 E3901.4.1 WALL COUNTERTOP SPACE.
 A RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH WALL
 COUNTERTOP SPACE 12 INCHES (305 MM) OR WIDER.
 RECEPTACLE OUTLETS SHALL BE INSTALLED SO THAT NO POINT
 ALONG THE WALL LINE IS MORE THAN 24 INCHES (610 MM),
 MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN THAT
 SPACE. [210.52(C)(1)
  
 GENERAL OUTLET SPACING DOES NOT APPEAR TO MEET THE
 CODE.
  
 E3901.2.1 SPACING.
 RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT
 MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL
 SPACE IS MORE THAN 6 FEET (1829 MM), FROM A RECEPTACLE
 OUTLET. [210.52(A)(1)]
  
 AN ADDITIONAL OUTLET IS REQUIRED AT THE REAR OF THE
 BUILDING.
  
 E3901.7 OUTDOOR OUTLETS.
 NOT LESS THAN ONE RECEPTACLE OUTLET THAT IS READILY
 ACCESSIBLE FROM GRADE LEVEL AND LOCATED NOT MORE THAN 6
 FEET, 6 INCHES (1981 MM) ABOVE GRADE, SHALL BE
 INSTALLED OUTDOORS AT THE FRONT AND BACK OF EACH
 DWELLING UNIT HAVING DIRECT ACCESS TO GRADE LEVEL.
 BALCONIES, DECKS, AND PORCHES THAT ARE ACCESSIBLE FROM
 INSIDE OF THE DWELLING UNIT SHALL HAVE AT LEAST ONE
 RECEPTACLE OUTLET INSTALLED WITHIN THE PERIMETER OF THE
 BALCONY, DECK, OR PORCH. THE RECEPTACLE SHALL BE
 LOCATED NOT MORE THAN 6 FEET, 6 INCHES (1981 MM) ABOVE
 THE BALCONY, DECK, OR PORCH SURFACE. [210.52(E)]
  
 SUBMIT A LOAD CALCULATION AND RISER DIAGRAM, SHOWINF
 LOCATION OF SERVICE AND PANEL.
  
 E3602.2SERVICE LOAD.
 THE MINIMUM LOAD FOR UNGROUNDED SERVICE CONDUCTORS AND
 SERVICE DEVICES THAT SERVE 100 PERCENT OF THE DWELLING
 UNIT LOAD SHALL BE COMPUTED IN ACCORDANCE WITH TABLE
 E3602.2. UNGROUNDED SERVICE CONDUCTORS AND SERVICE
 DEVICES THAT SERVE LESS THAN 100 PERCENT OF THE
 DWELLING UNIT LOAD SHALL BE COMPUTED AS REQUIRED FOR
 FEEDERS IN ACCORDANCE WITH CHAPTER 37. [220.82(A)
  
 SUBMIT A PANEL SCHEDULE
  
 E3706.2PANELBOARD CIRCUIT IDENTIFICATION.
 ALL CIRCUITS AND CIRCUIT MODIFICATIONS SHALL BE LEGIBLY
 IDENTIFIED AS TO THEIR CLEAR, EVIDENT, AND SPECIFIC
 PURPOSE OR USE. THE IDENTIFICATION SHALL INCLUDE AN
 APPROVED DEGREE OF DETAIL THAT ALLOWS EACH CIRCUIT TO
 BE DISTINGUISHED FROM ALL OTHERS. SPARE POSITIONS THAT
 CONTAIN UNUSED OVERCURRENT DEVICES OR SWITCHES SHALL BE
 DESCRIBED ACCORDINGLY. THE IDENTIFICATION SHALL BE
 INCLUDED IN A CIRCUIT DIRECTORY LOCATED ON THE FACE OF
 THE PANELBOARD ENCLOSURE OR INSIDE THE PANEL DOOR.
 CIRCUITS SHALL NOT BE DESCRIBED IN A MANNER THAT
 DEPENDS ON TRANSIENT CONDITIONS OF OCCUPANCY.
 [408.4(A)]
  
 SMOKE ALARMS SHALL BE LOCATED AT LEAST 3' FROM BATHROOM
 DOORS
  
 R314.3LOCATION.
 SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
  
 4.SMOKE ALARMS SHALL BE INSTALLED NOT LESS THAN 3 FEET
 (914 MM) HORIZONTALLY FROM THE DOOR OR OPENING OF A
 BATHROOM THAT CONTAINS A BATHTUB OR SHOWER UNLESS THIS
 WOULD PREVENT PLACEMENT OF A SMOKE ALARM REQUIRED BY
 SECTION R314.3.