| 2018-03-27 08:20:16 | FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| | NFPA 70 2014 EDITION |
| | |
| | JAKE LEAHY |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | KITCHEN COUINTER DOES NOT APPEAR TO MEET THE |
| | REQUIREMENTS OF THE CODE FOR SPACING |
| | |
| | E3901.4.1 WALL COUNTERTOP SPACE. |
| | A RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH WALL |
| | COUNTERTOP SPACE 12 INCHES (305 MM) OR WIDER. |
| | RECEPTACLE OUTLETS SHALL BE INSTALLED SO THAT NO POINT |
| | ALONG THE WALL LINE IS MORE THAN 24 INCHES (610 MM), |
| | MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN THAT |
| | SPACE. [210.52(C)(1) |
| | |
| | GENERAL OUTLET SPACING DOES NOT APPEAR TO MEET THE |
| | CODE. |
| | |
| | E3901.2.1 SPACING. |
| | RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT |
| | MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL |
| | SPACE IS MORE THAN 6 FEET (1829 MM), FROM A RECEPTACLE |
| | OUTLET. [210.52(A)(1)] |
| | |
| | AN ADDITIONAL OUTLET IS REQUIRED AT THE REAR OF THE |
| | BUILDING. |
| | |
| | E3901.7 OUTDOOR OUTLETS. |
| | NOT LESS THAN ONE RECEPTACLE OUTLET THAT IS READILY |
| | ACCESSIBLE FROM GRADE LEVEL AND LOCATED NOT MORE THAN 6 |
| | FEET, 6 INCHES (1981 MM) ABOVE GRADE, SHALL BE |
| | INSTALLED OUTDOORS AT THE FRONT AND BACK OF EACH |
| | DWELLING UNIT HAVING DIRECT ACCESS TO GRADE LEVEL. |
| | BALCONIES, DECKS, AND PORCHES THAT ARE ACCESSIBLE FROM |
| | INSIDE OF THE DWELLING UNIT SHALL HAVE AT LEAST ONE |
| | RECEPTACLE OUTLET INSTALLED WITHIN THE PERIMETER OF THE |
| | BALCONY, DECK, OR PORCH. THE RECEPTACLE SHALL BE |
| | LOCATED NOT MORE THAN 6 FEET, 6 INCHES (1981 MM) ABOVE |
| | THE BALCONY, DECK, OR PORCH SURFACE. [210.52(E)] |
| | |
| | SUBMIT A LOAD CALCULATION AND RISER DIAGRAM, SHOWINF |
| | LOCATION OF SERVICE AND PANEL. |
| | |
| | E3602.2SERVICE LOAD. |
| | THE MINIMUM LOAD FOR UNGROUNDED SERVICE CONDUCTORS AND |
| | SERVICE DEVICES THAT SERVE 100 PERCENT OF THE DWELLING |
| | UNIT LOAD SHALL BE COMPUTED IN ACCORDANCE WITH TABLE |
| | E3602.2. UNGROUNDED SERVICE CONDUCTORS AND SERVICE |
| | DEVICES THAT SERVE LESS THAN 100 PERCENT OF THE |
| | DWELLING UNIT LOAD SHALL BE COMPUTED AS REQUIRED FOR |
| | FEEDERS IN ACCORDANCE WITH CHAPTER 37. [220.82(A) |
| | |
| | SUBMIT A PANEL SCHEDULE |
| | |
| | E3706.2PANELBOARD CIRCUIT IDENTIFICATION. |
| | ALL CIRCUITS AND CIRCUIT MODIFICATIONS SHALL BE LEGIBLY |
| | IDENTIFIED AS TO THEIR CLEAR, EVIDENT, AND SPECIFIC |
| | PURPOSE OR USE. THE IDENTIFICATION SHALL INCLUDE AN |
| | APPROVED DEGREE OF DETAIL THAT ALLOWS EACH CIRCUIT TO |
| | BE DISTINGUISHED FROM ALL OTHERS. SPARE POSITIONS THAT |
| | CONTAIN UNUSED OVERCURRENT DEVICES OR SWITCHES SHALL BE |
| | DESCRIBED ACCORDINGLY. THE IDENTIFICATION SHALL BE |
| | INCLUDED IN A CIRCUIT DIRECTORY LOCATED ON THE FACE OF |
| | THE PANELBOARD ENCLOSURE OR INSIDE THE PANEL DOOR. |
| | CIRCUITS SHALL NOT BE DESCRIBED IN A MANNER THAT |
| | DEPENDS ON TRANSIENT CONDITIONS OF OCCUPANCY. |
| | [408.4(A)] |
| | |
| | SMOKE ALARMS SHALL BE LOCATED AT LEAST 3' FROM BATHROOM |
| | DOORS |
| | |
| | R314.3LOCATION. |
| | SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING |
| | LOCATIONS: |
| | |
| | 4.SMOKE ALARMS SHALL BE INSTALLED NOT LESS THAN 3 FEET |
| | (914 MM) HORIZONTALLY FROM THE DOOR OR OPENING OF A |
| | BATHROOM THAT CONTAINS A BATHTUB OR SHOWER UNLESS THIS |
| | WOULD PREVENT PLACEMENT OF A SMOKE ALARM REQUIRED BY |
| | SECTION R314.3. |