2018-03-22 18:54:08RESIDENTIAL (R3) ALTERATION, ADDITION BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017).
  
 1- ALL PLANS NEED TO HAVE THE ORIGINAL SEAL AND
 SIGNATURE OF THE PROFESSIONAL ARCHITECT OR PROFESSIONAL
 ENGINEER SHOWN ON PLANS AS REQUIRED BY CHAPTER 481 F.S.
 OR CHAPTER 471 F.S. RESPECTIVELY WHEN SUBMITTING
 DOCUMENTS FOR PUBLIC RECORDS.
 NOTE: BASED ON PLANS SUBMITTED, IT LOOKS LIKE THERE IS
 AN ARCHITECT AND AN ENGINEER WORKING IN THIS PROJECT.
 COORDINATE INFORMATION ON PLANS TO AVOID
 CONFLICTS/DELAYS.
  
 2- PLANS SUBMITTED WERE REDUCED IN SIZE. THEY ARE NOT
 LEGIBLE AND THE SCALE THEY WERE DRAWN IS NOT CORRECT
 ANY MORE. PROVIDE 2 COMPLETE SET OF PLANS THAT
 REPRESENT THE CORRECT SCALE. SEC. 107.2.1.3 CITY
 AMENDMENTS.
  
 3- THE CURRENT CODE IS THE FBC 6TH EDITION (2017) NOT
 THE FBC 5TH EDITION (2014). CHAPTER 553 FLORIDA
 STATUTE. UPDATE ALL PLANS AS REQUIRED.
  
 4- ACCORDING TO SEC. R301.2.1.4.3 FBC-RESIDENTIAL THIS
 BUILDING IS LOCATED IN EXPOSURE "C" NOT "B". REVISE AS
 REQUIRED INFORMATION IN PLANS AND REQUIRED AND REVISE
 THE DOORS AND WINDOWS DESIGN PRESSURES ACCORDINGLY.
  
 5- SITE PLAN SUBMITTED SHOWS "EXISTING COTTAGE TO
 REMAIN N.I.C.". ACCORDING TO CITY RECORDS THIS
 STRUCTURE WAS APPROVED AS A COTTAGE WITH GARAGE.
 PROPOSED ELEVATIONS SUBMITTED DON'T MATCH COTTAGE FLOOR
 PLAN. PROVIDE COMPLETE COTTAGE FLOOR PLAN WITH THE
 PROPOSED DESIGN. OTHERWISE REVISE FLOOR PLAN SHOWING
 THE ORIGINAL GARAGE. SEC. 107.2.1 CITY AMENDMENTS.
 NOTE: KITCHEN DRAWING ON SHEET A500 DOESN'T MATCH
 PROPOSED FLOOR PLAN. IS THIS FOR THE COTTAGE?. SAME
 THING APPLIES TO BATHROOM DRAWINGS ON SHEET A601. AND,
 WHAT ARE THE DWGS SHOWN ON SHEET A700 FOR?. ALSO, BUCK
 DETAILS SHOWN ON SHEET A400 DON'T APPLY TO THIS HOUSE.
 THIS IS A WOOD FRAMED HOUSE. REVISE AS REQUIRED.
  
 6- BEDROOM EGRESS WINDOWS DON'T COMPLY WITH SEC. R310.2
 FBC-RESIDENTIAL. REVISE AS REQUIRED. CLEARLY SPECIFY
 SIZE OF WINDOW THAT COMPLIES. SEE WINDOW PRODUCT
 APPROVAL FOR LISTED SIZES.
 R310.1 EMERGENCY ESCAPE AND RESCUE OPENING REQUIRED.
 BASEMENTS, HABITABLE ATTICS AND EVERY SLEEPING ROOM
 SHALL HAVE NOT LESS THAN ONE OPERABLE EMERGENCY ESCAPE
 AND RESCUE OPENING. WHERE BASEMENTS CONTAIN ONE OR MORE
 SLEEPING ROOMS, AN EMERGENCY ESCAPE AND RESCUE OPENING
 SHALL BE REQUIRED IN EACH SLEEPING ROOM. EMERGENCY
 ESCAPE AND RESCUE OPENINGS SHALL OPEN DIRECTLY INTO A
 PUBLIC WAY, OR TO A YARD OR COURT THAT OPENS TO A
 PUBLIC WAY.
  
 7- ENGINEERING PLANS ARE MISSING SHEET 6 OF 9. PROVIDE
 2 COMPLETE SETS. SEC. 107.1 CITY AMENDMENTS.
  
 8- SHEET 3 OF 9 IS MISSING THE FRAMING PLAN AT THE
 PROPOSED REAR PORCH. PROVIDE COMPLETE INFORMATION. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 9- SPECIFY ATTIC ACCESS SIZE AND LOCATION AT NEW
 ADDITION. SEC. R307.1 FBC-RESIDENTIAL.
  
 10- SPECIFY CARBON MONOXIDE ALARM WITHING ALL SLEEPING
 ROOMS AS REQUIRED BY SEC. R315.1 FBC-RESIDENTIAL.
 R315.1 CARBON MONOXIDE PROTECTION.
 EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING
 BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS
 ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR
 APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER
 FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE
 AS BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL
 CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH
 ROOM USED FOR SLEEPING PURPOSES.
  
 11- BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL,
 ONE SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO
 PALM BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS
 WITH THE IMPACT FEE STAMP AND A COPY OF THE PAID
 RECEIPT MUST BE RETURNED TO THE CITY BUILDING
 DEPARTMENT BEFORE THE BUILDING PERMIT CAN BE ISSUED.
 FOR INFORMATION CALL PALM BEACH COUNTY IMPACT FEES AT
 (561) 233-5025.
  
 12- SPECIFY ROOF VENTILATION AS REQUIRED BY SEC. R806
 FBC-RESIDENTIAL.
 R806.1 VENTILATION REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN OR SNOW. VENTILATION OPENINGS SHALL
 HAVE A LEAST DIMENSION OF 1/16 INCH (1.6 MM) MINIMUM
 AND 1/4 INCH (6.4 MM) MAXIMUM. VENTILATION OPENINGS
 HAVING A LEAST DIMENSION LARGER THAN 1/4 INCH (6.4 MM)
 SHALL BE PROVIDED WITH CORROSION-RESISTANT WIRE CLOTH
 SCREENING, HARDWARE CLOTH OR SIMILAR MATERIAL WITH
 OPENINGS HAVING A LEAST DIMENSION OF 1/16 INCH (1.6 MM)
 MINIMUM AND 1/4 INCH (6.4 MM) MAXIMUM. OPENINGS IN ROOF
 FRAMING MEMBERS SHALL CONFORM TO THE REQUIREMENTS OF
 SECTION R802.7. REQUIRED VENTILATION OPENINGS SHALL
 OPEN DIRECTLY TO THE OUTSIDE AIR.
  
 13- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. SEC. 109.3 CITY AMENDMENTS.
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 14- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) SINGLE HUNG WINDOWS AS SHOWN ON PLANS.
  
 B) WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY MARK
 MULLION SIZE TO VERIFY COMPLIANCE WITH THE CALCULATED
 DESIGN PRESSURES.
  
 C) PEEL & STICK ROOF UNDERLAYMENT FOR SHINGLES AS
 SPECIFIED ON WALL SECTIONS.
  
 D) ROOF SHINGLES AS SHOWN ON PLANS.
  
 E) INSWING ENTRY DOOR WITH SIDELITE AS SHOWN ON PLANS.
  
 F) INSWING MUD ROOM DOOR AS SHOWN ON PLANS.
  
 G) ALL OUTSWING FRENCH DOORS AS SHOWN ON PLANS.
  
 H) GABLE END VENTS AS SHOWN ON PLANS.
  
 I) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. NOTE: PROVIDE ONLY THE FLORIDA PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED
 CONNECTOR OR DESIGN PROFESSIONAL TO LIST THE FLORIDA
 PRODUCT APPROVAL NUMBER NEXT TO EACH SPECIFIED
 CONNECTOR.
  
 J) STORAGE DOUBLE DOORS AS SHOWN ON PLANS.
  
 K) HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
  
 15- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DON?T STAPLE OLD DRAWINGS TO PLANS.
  
  