Plan Review Notes
Plan Review Notes For Permit 18030010
Permit Number 18030010
Review Stop B
Sequence Number 1
Notes
Date Text
2018-03-06 17:38:52PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE SCOPE OF WORK FOR THIS PERMIT IS FOR THE
 INTERIOR REMODEL OF THE MAIN HOUSE AND A GUEST HOUSE.
 THE PLANS THAT ARE ON FILE DO NOT INDICATE THAT ANY
 HVAC WORK OTHER THAN INSTALLATION OF BATH, KITCHEN AND
 DRYER EXHAUST IN THE MAIN HOUSE. NO ENERGY FORMS WERE
 REQUIRED. PLEASE CLARIFY WHY YOU ARE SUBMITTING ENERGY
 FORMS AND EQUIPMENTS SIZING CALCULATIONS UNDER THIS
 PERMIT. FBC 107.2.1
  
 2) THE FORMS THAT WERE SUBMITTED ARE FOR THE 2017 FBC
 (FORM R405-2017), THIS PROJECT IS PERMITED UNDER THE
 2014 FBC (FORM R405-2014).
  
 3) THERE ARE TWO BUILDINGS AT THIS LOCATION. SPECIFY
 EITHER MAIN HOUSE OR GUEST HOUSE ON THE FORMS. FBC
 107.2.1
  
 4) THERE WAS NO ADDITION IN THE SCOPE OF WORK FOR THIS
 PROJECT. IF THERE IS AN ADDITION, THEN THE PLANS WILL
 BE REQUIRED TO HAVE AN IMPACT FEE REVIEW. FBC 107.2.1
  
 5) BOTH OF THE STRUCTURES HAVE BEDROOMS AND NO BEDROOMS
 IS SPECIFIED ON THE FORMS. CLARIFY. FBC 107.2.1
  
 6) THE OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE
 FORMS. FBC ENERGY CONSERVATION R103.1.1.2
  
 7) SUBMIT THE COMPLETE EQUIPMENT SIZING CALCULATIONS
 NOT JUST THE SUMMARY PAGE. FBC 107.2.1.3
  