| Plan Review Notes For Permit 18021234 |
| Permit Number |
18021234 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-03-01 12:25:38 | DENIED | | | | | | 1. YOUR DEVICE DOES NOT MEET THE CROSS CONNECTION | | | STANDARDS SET BY WPB PLEASE PROVIDE DOCUMENTATION THAT | | | THE PROPOSED BACKFLOW DEVICE IS ON THE APPROVED DEVICE | | | LIST PUBLISHED BY THE UNIVERSITY OF SOUTHERN CALIFORNIA | | | (USC). | | | | | | 2. ALL BACKFLOW DEVICES MUST BE LEAD-FREE. LEAD-FREE | | | (LF) SHALL BE INCLUDED IN THE SERIAL NUMBER OR STAMPED | | | ON THE BODY OF THE DEVICE. ANY DEVICE THAT HAS BEEN | | | ALTERED AFTER BEING ASSEMBLED BY THE MANUFACTURER WILL | | | NOT BE APPROVED. I HAVE GONE TO AMES WEBSITE TO | | | RESEARCH IT AND THIS DEVICE IS STAINLESS STEEL. ON YOUR | | | SUBMITTAL SHEET IT DOES REFER TO IT BEING LEAD-FREE BUT | | | THAT IS THE BODY ONLY. THE VALVE AT EACH END MAY HAVE | | | LEAD CONTENT AND THIS IS WHY THE UNIVERSITY OF SOUTHERN | | | CALIFONIA HAS NOT APPROVED IT. | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | | | | LUIS A. CRESPO | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | [email protected] |
|