| 2018-04-03 09:06:38 | 1ST REVIEW FBC-2017 MECHANICAL, WEST PALM BEACH |
| | AMENDMENTS TO THE FBC-17 |
| | PERMIT #18021230 |
| | 4/3/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) REQUIRED SUBMITTALS TO BE PROVIDED PRIOR TO |
| | PERMITTING: |
| | |
| | A) GENERATOR |
| | B) GENERATOR EXHAUST PIPING |
| | C) BACKPRESSURE CALCULATIONS FOR EXHAUST PIPING. |
| | D) NOA'S FOR THE EXHAUST LOUVER, SUPPLY FANS, EXHAUST |
| | FAN, FAN CURBS, AND EXHAUST PIPE SUPPORTS AND BRACKETS. |
| | E) FUEL PIPING. |
| | |
| | 2) SHEET M1.3: ADDITIONAL INFORMATION REQUIRED: |
| | |
| | A) THE TOTAL RUN LENGTH OF THE EXHAUST PIPE AND THE |
| | LENGTH OF EACH SEGMENT FROM ELBOW TO ELBOW. |
| | B) MAX BACK PRESSURE FROM THE MANUFACTURER. |
| | C) BACKPRESSURE CALCULATIONS FOR THE EXHAUST PIPE RUN. |
| | D) TYPES AND SPACINGS OF HORIZONTAL AND VERTICAL PIPE |
| | SUPPORTS. |
| | E) FASTENING AND ANCHORING DETAILS FOR EXHAUST PIPE |
| | SUPPORTS AND BRACKETS. |
| | F) SHOP DRAWINGS FOR THE VERTICAL VENT PIPE COVER TO BE |
| | INSTALLED ABOVE THE ROOF INCUDING ANCHORING AND |
| | FASTENING DETAILS. |
| | |
| | 3) PLEASE NOTE THAT ALL PRODUCT SUBMITTALS SHALL BE |
| | REVIEWED AND APPROVED BY THE ENGINEER OF RECORD. PLEASE |
| | REVIEW THE FOLLOWING WPB AMENDMENT PERTAINING TO |
| | DEFERRED SUBMITTALS. |
| | |
| | DEFERRED SUBMITTAL: 107.3.4.2 DEFERRED SUBMITTALS. FOR |
| | THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE |
| | DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT |
| | SUBMITTED AT THE TIME OF THEAPPLICATION AND THAT ARE TO |
| | BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A |
| | SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL |
| | HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION |
| | DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |