Plan Review Notes
Plan Review Notes For Permit 18021230
Permit Number 18021230
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2018-03-28 16:26:01THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 0.0 - THERE ARE REFERENCES TO APPLICABLE
 NFPA CODES; HWEVER, NFPA 37 IS NOT INDICATED
  
 PER NFPA 110:
  
 7.10 EXHAUST SYSTEM.
 7.10.1 THE EXHAUST SYSTEM EQUIPMENT AND INSTALLATION,
 INCLUDING
 PIPING, MUFFLER, AND RELATED ACCESSORIES, SHALL BE IN
 ACCORDANCE WITH NFPA37, STANDARD FOR THE INSTALLATION
 AND USE OF
 STATIONARY COMBUSTION ENGINES AND GAS TURBINES, AND
 OTHER APPLICABLE
 STANDARDS.
  
 PLEASE REVIEW TO ENSURE COMPLIANCE AND ADD THE
 INDICATED REFERENCE.
  
  
  
  
 2) MECHANICAL SHEETS - THERE IS NO INDICATIONS OF THE
 FOLLOWING:
  
 PER NFPA 110:
  
 7.10.3* EXHAUST PIPING SHALL BE CONNECTED TO THE PRIME
 MOVER
 BY MEANS OF A FLEXIBLE CONNECTOR AND SHALL BE
 INDEPENDENTLY
 SUPPORTED THEREAFTER SO THAT NO DAMAGING WEIGHT OR
 STRESS IS
 APPLIED TO THE ENGINE EXHAUST MANIFOLD OR TURBOCHARGER.
 7.10.3.1 A CONDENSATE TRAP AND DRAIN VALVE SHALL BE
 PROVIDED
 AT THE LOW POINT(S) OF THE PIPING UNLESS THE PIPING IS
 SELFDRAINING.
  
  
  
 3) PRODUCT SPEC SHEETS - THERE ARE NO PRODUC SPEC
 SHEETS INDICATING COMLIANCE WITH THE FOLLOWING:
  
 PER NFPA 37:
  
 CHAPTER 8 ENGINE EXHAUST SYSTEMS
 8.1 DESIGN AND CONSTRUCTION.
 8.1.1* ENGINE EXHAUST SYSTEMS SHALL BE DESIGNED AND
 CONSTRUCTED
 SUCH THAT THE SYSTEM CAN WITHSTAND THE ANTICIPATED
 EXHAUST GAS TEMPERATURES.
 8.1.2* EXHAUST SYSTEMS SHALL BE DESIGNED AND
 CONSTRUCTED TO
 WITHSTAND THE INTENDED SERVICE.
  
 8.1.4* EXHAUST SYSTEMS SHALL BE DESIGNED AND
 CONSTRUCTED TO
 WITHSTAND FORCES CAUSED BY THE IGNITION OF UNBURNED
 FUEL OR
 SHALL HAVE PROVISIONS TO RELIEVE THOSE FORCES WITHOUT
 DAMAGING
 THE EXHAUST SYSTEM.
 8.1.5* LOW POINTS IN EXHAUST SYSTEMS SHALL HAVE DRAINS.
  
 8.3 CLEARANCE FROM EXHAUST SYSTEMS WITH EXHAUST GAS
 TEMPERATURES
 OF LESS THAN 760?C (1400?F).
  
 8.4* CLEARANCE FROM EXHAUST SYSTEMS WITH EXHAUST GAS
 TEMPERATURES
 OF 760?C (1400?F) OR GREATER. EXHAUST SYSTEMS WITH
 EXHAUST GAS TEMPERATURES OF 760?C (1400?F) OR GREATER
 SHALL
 COMPLY WITH NFPA 211, STANDARD FOR CHIMNEYS,
 FIREPLACES, VENTS,
 AND SOLID FUEL?BURNING APPLIANCES.
  
 PLEASE REVIEW AND PROVIDE SHEPC SHEETS OR SPECIFIC
 DETAILS INDICATING COMPLIANCE.
  
  
  
 4) GENERATOR SPEC SHEETS - THERE ARE NO GENERATOR SPEC
 SHEETS INDICATING THAT THE TYPE , SIZE AND LENGTH OF
 THE PROPOSED EXHAUST MEETS THEIR SPECIFICATIONS.
  
 PLEASE PROVIDE THE SPEC SHEETS AND/OR SPECIFIC DETAILS
 OF COMPLIANCE.
  
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  