| 2018-03-28 16:26:01 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET A 0.0 - THERE ARE REFERENCES TO APPLICABLE |
| | NFPA CODES; HWEVER, NFPA 37 IS NOT INDICATED |
| | |
| | PER NFPA 110: |
| | |
| | 7.10 EXHAUST SYSTEM. |
| | 7.10.1 THE EXHAUST SYSTEM EQUIPMENT AND INSTALLATION, |
| | INCLUDING |
| | PIPING, MUFFLER, AND RELATED ACCESSORIES, SHALL BE IN |
| | ACCORDANCE WITH NFPA37, STANDARD FOR THE INSTALLATION |
| | AND USE OF |
| | STATIONARY COMBUSTION ENGINES AND GAS TURBINES, AND |
| | OTHER APPLICABLE |
| | STANDARDS. |
| | |
| | PLEASE REVIEW TO ENSURE COMPLIANCE AND ADD THE |
| | INDICATED REFERENCE. |
| | |
| | |
| | |
| | |
| | 2) MECHANICAL SHEETS - THERE IS NO INDICATIONS OF THE |
| | FOLLOWING: |
| | |
| | PER NFPA 110: |
| | |
| | 7.10.3* EXHAUST PIPING SHALL BE CONNECTED TO THE PRIME |
| | MOVER |
| | BY MEANS OF A FLEXIBLE CONNECTOR AND SHALL BE |
| | INDEPENDENTLY |
| | SUPPORTED THEREAFTER SO THAT NO DAMAGING WEIGHT OR |
| | STRESS IS |
| | APPLIED TO THE ENGINE EXHAUST MANIFOLD OR TURBOCHARGER. |
| | 7.10.3.1 A CONDENSATE TRAP AND DRAIN VALVE SHALL BE |
| | PROVIDED |
| | AT THE LOW POINT(S) OF THE PIPING UNLESS THE PIPING IS |
| | SELFDRAINING. |
| | |
| | |
| | |
| | 3) PRODUCT SPEC SHEETS - THERE ARE NO PRODUC SPEC |
| | SHEETS INDICATING COMLIANCE WITH THE FOLLOWING: |
| | |
| | PER NFPA 37: |
| | |
| | CHAPTER 8 ENGINE EXHAUST SYSTEMS |
| | 8.1 DESIGN AND CONSTRUCTION. |
| | 8.1.1* ENGINE EXHAUST SYSTEMS SHALL BE DESIGNED AND |
| | CONSTRUCTED |
| | SUCH THAT THE SYSTEM CAN WITHSTAND THE ANTICIPATED |
| | EXHAUST GAS TEMPERATURES. |
| | 8.1.2* EXHAUST SYSTEMS SHALL BE DESIGNED AND |
| | CONSTRUCTED TO |
| | WITHSTAND THE INTENDED SERVICE. |
| | |
| | 8.1.4* EXHAUST SYSTEMS SHALL BE DESIGNED AND |
| | CONSTRUCTED TO |
| | WITHSTAND FORCES CAUSED BY THE IGNITION OF UNBURNED |
| | FUEL OR |
| | SHALL HAVE PROVISIONS TO RELIEVE THOSE FORCES WITHOUT |
| | DAMAGING |
| | THE EXHAUST SYSTEM. |
| | 8.1.5* LOW POINTS IN EXHAUST SYSTEMS SHALL HAVE DRAINS. |
| | |
| | 8.3 CLEARANCE FROM EXHAUST SYSTEMS WITH EXHAUST GAS |
| | TEMPERATURES |
| | OF LESS THAN 760?C (1400?F). |
| | |
| | 8.4* CLEARANCE FROM EXHAUST SYSTEMS WITH EXHAUST GAS |
| | TEMPERATURES |
| | OF 760?C (1400?F) OR GREATER. EXHAUST SYSTEMS WITH |
| | EXHAUST GAS TEMPERATURES OF 760?C (1400?F) OR GREATER |
| | SHALL |
| | COMPLY WITH NFPA 211, STANDARD FOR CHIMNEYS, |
| | FIREPLACES, VENTS, |
| | AND SOLID FUEL?BURNING APPLIANCES. |
| | |
| | PLEASE REVIEW AND PROVIDE SHEPC SHEETS OR SPECIFIC |
| | DETAILS INDICATING COMPLIANCE. |
| | |
| | |
| | |
| | 4) GENERATOR SPEC SHEETS - THERE ARE NO GENERATOR SPEC |
| | SHEETS INDICATING THAT THE TYPE , SIZE AND LENGTH OF |
| | THE PROPOSED EXHAUST MEETS THEIR SPECIFICATIONS. |
| | |
| | PLEASE PROVIDE THE SPEC SHEETS AND/OR SPECIFIC DETAILS |
| | OF COMPLIANCE. |
| | |
| | |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |