| 2018-03-28 10:44:51 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. THE NEC AND FBC SPECIFIED FOR DESIGN ON SHEET E0.1 |
| | IS NOT THE CURRENT CODE. PROVIDE CORRECTION. FBC |
| | PREFACE (ALSO SEE CURRENT CODES ABOVE) |
| | 2. PROVIDE LISTING FOR RECONDITIONED 2000 AMP BREAKER. |
| | NEC110.3 |
| | 3. PROVIDE GFI PROTECTION FOR 2000 AMP BREAKER AND |
| | DOWNSTREAM PANELS WHERE APPLICABLE. NEC 230.95, 517.17 |
| | 4. PLAN STATES THAT THE LOADING OF THE GENERATOR IS |
| | BASED ON A 3 MONTH STUDY FROM OCTOBER THROUGH DECEMBER |
| | OF 2016. PER NEC 517.30(D): ?THE ESSENTIAL ELECTRICAL |
| | SYSTEM SHALL HAVE THE CAPACITY AND RATING TO MEET THE |
| | MAXIMUM ACTUAL DEMAND LIKELY TO BE PRODUCED BY THE |
| | CONNECTED LOAD.? THE TIME PERIOD DESCRIBED FOR THE |
| | STUDY DOES NOT SEEM TO BE THE TIME OF YEAR WHERE THE |
| | MAXIMUM DEMAND WOULD BE ENCOUNTERED. PROVIDE |
| | CLARIFICATION AND/OR CORRECTION OF THE DEMAND LOAD FOR |
| | THE GENERATOR. THIS REVIEWER FEELS THAT LOOKING AT 12 |
| | MONTHS OF HISTORY WOULD GIVE A BETTER REPRESENTATION OF |
| | THE LIKELY DEMAND. NEC 517.30(D) |
| | 5. PROVIDE DETAILS OF COMPLIANCE WITH NEC 240.87. |
| | 6. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, |
| | DAS, LIGHTNING PROTECTION, COMMERCIAL HOOD SYSTEMS, |
| | WALK IN COOLERS, SIGNS, SITE LIGHTING, AND SWIMMING |
| | POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE |
| | OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING |
| | THE REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION |
| | SHEET SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB |
| | FBC 105.1, 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |