| 2018-03-26 14:40:59 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 18021230 |
| | ADD: 901 45TH ST. |
| | CONT: WESTBROOKE CORPORATION |
| | TEL: 561-395-4126 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MONDAY MARCH 26, 2018 |
| | ACTION: DENIED |
| | |
| | 1A) SHEET A1.1 NOTE # 1 INDICATES NEW WALL LOUVERS . |
| | SHEET M1.1 INDICATES THE INSTALLATION OF (2) LOUVERS, |
| | ONE 10 FOOT WIDE X 8 FEET TALL AND THE OTHER A 2 X2 |
| | FOOT MAKE UP AIR LOUVER. PLEASE SUBMIT PRODUCT |
| | APPROVALS TO COMPLY WITH: |
| | 2017 FBC-B 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA |
| | DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE |
| | 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY |
| | OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| | PRODUCT APPROVALS: |
| | (31)(C) WALL LOUVERS. |
| | |
| | 1B) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | 2) A MIAMI-DADE NOA 17-0320.06 A STEEL CRAFT H SERIES |
| | FLUSH OUTSWING COMMERCIAL DOOR W/ WO PANIC EXIT LMI WAS |
| | SUBMITTED PLEASE IDENTIFY ON SHEET 1 OF 13 WHICH DOOR |
| | IS TO BE INSTALLED WITH THE APPROPRIATE PRESSURES. |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED TO |
| | DETERMINE CODE COMPLIANCE FOR PRESSURES. |
| | |
| | 3) A MIAMI-DADE NOA 16-0413.21 JOHNS MANVILLE MODIFIED |
| | BITUMEN ROOFING SYSTEMS OVER STEEL DECKS WAS SUBMITTED. |
| | THIS REPORT HAS 78 PAGES WITHIN THE REPORT. |
| | FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL ROOFING |
| | SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR ROOF |
| | ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, IF |
| | ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3. |
| | FASTENER DENSITIES SHALL BE INCREASED FOR BOTH |
| | INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE |
| | WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION |
| | PREPARED, SIGNED AND |
| | SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR |
| | REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. |
| | |
| | 4A) SHEET A2.1 AND SHEET M1.1 BOTH SHOW NEW NOA RATED |
| | ROOF PROPELLER SUPPLY FANS WITH HOODS. THIS REVIEW NO |
| | SUCH PRODUCT APPROVALS WERE SUBMITTED. PLEASE PROVIDE |
| | COMPLIANCE WITH: |
| | 2017 FBC-B SECTION 1609.6.4.4.1 COMPONENTS & CLADDING. |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE |
| | CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31) (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP |
| | VENTILATORS, ETC. |
| | |
| | 4B) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | 5A) SHEET A2.2 AND S-100 BOTH SHOW NEW ROOF TOP CURBS |
| | THAT THE ROOF TOP FANS SIT ON. S-100 DETAIL 01 ROOF |
| | SECTION INDICATES THE ROOF TOP CURBS WILL NEED TO |
| | PROVIDE A NOA, A MIAMI-DADE NOTICE OF ACCEPTANCE |
| | REPORT, NONE WERE SUBMITTED. PLEASE PROVIDE COMPLIANCE |
| | WITH: |
| | 2017 FBC-B SECTION 1609.6.4.4.1 COMPONENTS & CLADDING. |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE |
| | CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31) (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP |
| | VENTILATORS, ETC. |
| | |
| | 5B) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | 5C) SHEET S-100 DETAIL 01 INDICATES THE ROOF TOP FANS |
| | TO CURB AS PER THE MANUFACTURERS RECOMMENDATIONS. FOR |
| | ALL ROOF TOP EQUIPMENT, CURBS, FANS OR VENTILATORS, |
| | DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL |
| | AS FROM THE CURB TO THE EQUIPMENT ABOVE. |
| | |
| | 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| | MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| | METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| | EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| | AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| | EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| | OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| | SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| | LOADS. |
| | |
| | 6 SHEET A2.1 NOTE # 8 INDICATES NEW EXHAUST DUCT COVER |
| | AND REFERS TO SHEET A2.2 DETAIL # 5. THERE IS NO |
| | MENTION ON THE STRUCTURAL SHEETS OF THE NEW EXHAUST |
| | DUCT COVER. THE SHEET M1.2 NOTES 6 & 8 BOTH MAKE |
| | REFERENCE TO THE EXTERIOR DUCT AND COVER TO BE ANCHORED |
| | TO THE BUILDING TO RESIST HURRICANE FORCE WINDS, 180 |
| | MPH VULT, CATEGORY III BUILDING. PLEASE PROVIDE |
| | ADDITIONAL INFORMATION TO BE ABLE TO SHOW CODE |
| | COMPLIANCE. 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 7) THE STRUCTURAL SHEET DOES NOT MENTION HOW THE 16 |
| | INCH VENT THAT EXTENDS UP THE 3 STORY BUILDING AND 10 |
| | FEET ABOVE THE PENTHOUSE LEVEL IS TO BE SECURED AGAINST |
| | HURRICANE FORCE WINDS (180 MPH VULT). SHEET M1.3 THE |
| | PENTHOUSE DETAIL MENTIONS THIS BUT NEITHER SHEET |
| | PROVIDES AN ENGINEERING DETAIL HOW THIS WILL BE |
| | ACCOMPLISHED. |
| | FOR ALL ROOF TOP EQUIPMENT, CURBS, FANS OR A/C STANDS, |
| | AND OR VENTS, DETAILED ATTACHMENT TO THE ROOF FRAMING & |
| | DECK AS WELL AS FROM THE CURB OR ROOF STAND TO THE |
| | EQUIPMENT ABOVE. |
| | |
| | 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| | MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| | METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| | EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| | AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| | EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| | OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| | SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| | LOADS. |
| | |
| | 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, CBO |