| Plan Review Notes For Permit 18021227 |
| Permit Number |
18021227 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-03-05 17:02:53 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) IT APEARS THAT SMOKE DAMPERS ARE DEING REMOVED | | | WITHOUT JUSTIFICATION. | | | | | | THE ENGINEERED LIFE SAFETY SYSTEMS WAS DESIGNED TO | | | FUNCTION A CERTAIN WAY BY THE EOR OF THIS BUILDING. IT | | | IS UNCLEAR WHAT THE SCOPE OF WORK OF THIS REVISION IS | | | AND HOW IT AFFECTES THE OVERALL LIFE SAFETY OF THIS | | | BUILDING. | | | | | | HOIW DID THE EXISTING SMOKE DAMPERS WORK AND WHAT DID | | | THEY DO? WHAT IS BEING PROVIDED TO EQUAL THEIR | | | FUNCTION? | | | | | | PLEASE REVIEW AND PROVIDE DETAILS. | | | | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | | | | |
|