| 2018-05-23 17:17:21 | 2ND REVIEW FBC-2017 MECHANICAL, EXISTING BUILDING, |
| | ENERGY CONSERVATION CODES |
| | PERMIT #18021224 |
| | 5/23/2018 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | THIS FOLLOW-UP (2ND) ) REVIEW IS BASED ON THE |
| | RESUBMITTED PLANS, DOCUMENTS, AND RESPONSE NARRATIVE BY |
| | THE ENGINEER OF RECORD. |
| | ALL PREVIOUS REVIEW COMMENTS NOT COMPLETELY RESOLVED |
| | ARE LISTED BELOW IN THEIR ORIGINAL NUMERICAL ORDER. |
| | |
| | 4) THE SUBMITTED SPECS FOR THE CHILLER ARE FOR A |
| | SMALLER MODEL THEN THE ONE LISTED ON SHEET M-1. PLEASE |
| | SUBMIT THE CORRECT SPECIFICATION SHEETS. |
| | |
| | 5) M-2: THE SPLIT SYSTEM SCHEDULE SHOWS AN INSUFFICIENT |
| | AMOUNT OF OUTSIDE AIR BEING SUPPLED TO THE BAR AND |
| | TASTING ROOM AREAS- 630 CFMS SUPPLIED BUT 1035 CFMS |
| | REQUIRED PER THE OUTSIDE AIR CALCULATION. |
| | |
| | 8) THE ARCHITECT IS STATING IN HS RESPONSE NARRATIVE |
| | THAT THE BREWHOUSE AND ALL OTHER BREWEY TANKS AND |
| | EQUIPMENT ARE TO BE DEFFERRED SUBMITTALS, HOWEVER CUT |
| | SHEETS AND HAVE BEEN SUBMITTED FOR THE TANKS AND |
| | INFORMATION HAS ALSO BEEN PLACED ON SHEET M-1. AS |
| | PREVIOUSLY NOTED, PLEASE REFER TO SECTION1003.1 FBC-17 |
| | MECHANICAL: IF THE TANKS ARE DETERMINED TO BE |
| | CLASSIFIED AS |
| | |
| | PRESSURE VESSELS, THEY SHALL BE CONSTRUCTED AND |
| | CERTIFIED IN ACCORDANCE WITH ASME BOILER AND PRESSURE |
| | VESSEL CODE. NEITHER THE PLANS OR CUT SHEETS ARE |
| | VERIFYING COMPLIANCE. |
| | |
| | 11) AS PREVIOUSLY REQUESTED PROVIDE A FLORIDA PRODUCT |
| | APPROVAL OR MIAMI-DADE NOA FOR THE O/A LOUVERS- RULE |
| | 9N-3 FAC. PLEASE NOTE THAT THE NOA #16-0201.03 SHOWN ON |
| | THE PLAN FOR THE LOUVERS HAS EXPIRED. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |