| 2018-04-05 11:20:03 | FIRST REVIEW |
| | |
| | 1). SHOW THE DIMENSIONS OF THE REQUIRED CLEAR FLOOR |
| | SPACES FOR THE HANDICAPPED ACCESSIBLE FIXTURES. COMPLY |
| | WITH 2017 FBC-ACCESS. SECS. 604.3 FOR WATER CLOSETS AND |
| | 606.2 AND 305.3 FOR LAVATORIES. |
| | 2) THE HEIGHT OF ACCESSIBLE LAVATORIES SHALL COMPLY |
| | WITH 2017 FBC-ACCESS. SEC. 606.3. |
| | 3) MIRRORS SHALL COMPLY WITH 2017 FBC-ACCESS. SEC. |
| | 603.3. |
| | 4) THE HEIGHT OF SOAP DISPENSERS, HAND DRYERS, PAPER |
| | TOWEL DISPENSERS SHALL COMPLY WITH 2017 FBC-ACCESS. |
| | CODE SEC. 308. |
| | 5) THE LOCATION AND THE HEIGHT OF THE GRAB BARS FOR THE |
| | WATER CLOSETS SHALL COMPLY WITH 2017 FBC-ACCESS. SECS. |
| | 604.5.1, 604.5.2, 609.4. SHOW THE LOCATION AND MOUNTING |
| | HEIGHT DIMENSIONS ON THE PLANS. |
| | 6) TOILET PAPER DISPENSERS SHALL BE LOCATED PER 2017 |
| | FBC- ACCESS. SEC. 604.7. SHOW THIS ON THE PLANS |
| | 7) SHT. A2.2 - THE STANDARD TOILET STALL IN THE WOMEN'S |
| | RESTROOM SHALL BE A MINIMUM OF 60 INCHES FOR FLOOR |
| | MOUNTED WATER CLOSETS. 2017 FBC-PLUMBING SEC.405.3.1. |
| | 8) PLEASE PROVIDE A LEGEND FOR THE ACRONYMS FOR THE |
| | TANKS. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 9) INDICATE THE PREVIOUS OCCUPANCY ON THE LIFESAFETY |
| | PLANS. INDICATE ON THE PLANS IF THIS IS A CHANGE OF |
| | OCCUPANCY. IF SO, THE STRUCTURE SHALL COMPLY WITH THE |
| | REQUIREMENTS OF THE 2017 FBC - EXISTING BUILDING CODE. |
| | 10) THE LAVATORY OUTSIDE OF THE TOILET COMPARTMENT |
| | SHALL COMPLY WITH 2017 FBC-ACCESS. SECS. 213.3.4, 606. |
| | 11) THE URINAL IN THE MEN'S RESTROOM IS LOCATED IN THE |
| | LINE OF SIGHT OF THE RESTROOM DOOR. IN THE OPEN DOOR |
| | POSITION, THE USER AT THE URINAL DOES NOT APPEAR TO |
| | HAVE ADEQUATE PRIVACY AS REQD. IN THE 2017 FBC-PLUMBING |
| | SEC.405.3.5. SHOW THE LENGTH OF THE URINAL PARTITIONS |
| | AND THEY SHALL EXTEND FROM THE WALL SURFACE AT EACH |
| | SIDE OF THE URINAL NOT LESS THAN 18 INCHES OR TO A |
| | POINT NOT LESS THAN 6 INCHES BEYOND THE OUTERMOST FRONT |
| | LIP OF THE URINAL MEASURED FROM THE FINISHED BACK WALL |
| | SURFACE, WHICHEVER IS GREATER. |
| | 12) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | TANKLESS WATER HEATER. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 13) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | BREWERY TANKS. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 14) SUBMIT A PIPING DETAIL FOR ALL THE PROCESS PIPING |
| | FOR ALL THE TANKS INVOLVED IN THE BREWING PROCESS AND |
| | THE KEG WASHER. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 15) THE GAS LINE FROM THE METER TO THE FIRT TEE SHALL |
| | BE A MINIMUM OF 1 1/2 INCHES PER TABLE 402.4 (2) OF THE |
| | 2017 FBC-FUEL GAS CODE. |
| | 16) THE T & P LINE FROM THE WATER HEATER SHALL |
| | DISCHARGE THROUGH AN AIR GAP LOCATED IN THE SAME ROOM |
| | AS THE WATER HEATER. 2017 FBC-PLUMBING SEC. 504.6 (2). |
| | 17) A BACKFLOW DEVICE IS REQUIRED AT THE METER PER THE |
| | CITY OF WPB CROSS CONNECTION CONTROL MANUAL. A MINIMUM |
| | OF A REDUCED PRESSURE ZONE DEVICE IS REQUIRED. A |
| | SEPARATE PERMIT AND MANUFACTURER'S SPECIFICATIONS SHALL |
| | BE SUBMITTED FOR REVIEW. |
| | 18) SUBMIT DETAILS FOR THE 8 INCH AND 10 INCH VENTS FOR |
| | THE BREWHOUSE TANKS SHOWN ON SHT. M-1. |
| | 19) SUBMIT A DETAIL SHOWING THE TYPE OF VENT, LOCATION, |
| | SIZE, TERMINATION POINT, HEIGHT ABOVE THE ROOF AND |
| | ANCHORING DETAILS OF THE GAS VENT(S) PER 2017 FBC-FUEL |
| | GAS SECS. 502 THRU 505 OR 2017 FBC-RES. SEC.G2426 |
| | THROUGH G2439. |
| | 20) INDIRECT WASTE PIPING THAT EXCEEDS 30 INCHES IN |
| | DEVELOPED LENGTH MEASURED HORIZONTALLY OR 54 INCHES IN |
| | TOTAL DEVELOPED LENGTH SHALL BE TRAPPED. 2017 |
| | FBC-PLUMBING SEC.802.2. ( SEE TRENCH DRAINS) |
| | 21) SUBMIT DOCUMENTATION FOR THE TYPE OF WASTE THAT |
| | WILL BE DISCHARGED INTO THE TRENCH DRAIN AND ALSO FROM |
| | THE KEG WASHER. DEPENDING ON THE TYPE OF WASTE, AN |
| | INTERCEPTOR OR SEPARATOR MAY BE REQUIRED IN THE DRAIN |
| | LINE FROM THESE AREAS. 2017 FBC-PLUMBING SEC.1003.1. |
| | 22) THE HOT WATER RECIRULATION MAIN AND THE FIRST EIGHT |
| | FEET OF ANY BRANCKES SHALL BE INSULATED WITH INSULATION |
| | WITH A MINIMUM OF 1 INCH WALL THICKNESS. 2017 |
| | FBC-ENERGY SEC.C404.4.THIS INCLUDES THE RECIRCULATION |
| | IN THE SLEEVE UNDER THE SLAB. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |