| 2018-03-27 15:14:53 | PERMIT # 18021224 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | FAILED COMMENTS: |
| | |
| | 1) UPDATE THE CODE LIST TO REFERENCE THE 6TH EDITION OF |
| | THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE |
| | 2015 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA |
| | AMENDMENTS. |
| | |
| | 2) PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION |
| | SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND |
| | RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION |
| | SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A |
| | 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A |
| | FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED |
| | BY EMAIL ([email protected]) OR IN WRITING (FAX: |
| | 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE |
| | MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.? |
| | |
| | 3) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE |
| | INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER |
| | SYSTEM AND/OR FIRE ALARM SYSTEM. |
| | |
| | 4) EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS |
| | SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A |
| | CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM. |
| | SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF |
| | OCCUPANTS PERMITTED FOR EACH ROOM. |
| | |
| | 5) FOR ASSEMBLY AND EDUCATIONAL OCCUPANCIES WITH AN |
| | OCCUPANT LOAD OF 100 OR MORE PERSONS (50 PERSONS PER |
| | THE FLORIDA BUILDING CODE), PANIC HARDWARE SHALL BE |
| | PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH. NO OTHER |
| | LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT BE |
| | RELEASED BY THE PANIC HARDWARE. AS A SUBSTITUTE FOR |
| | PANIC HARDWARE, THE MAIN ENTRANCE IS PERMITTED TO HAVE |
| | AN INTERIOR KEYED DOOR LOCK (AND NO LATCH) WITH A |
| | READILY VISIBLE SIGN STATING THIS DOOR TO REMAIN |
| | UNLOCKED WHEN THE BUILDING IS OCCUPIED. SIGN LETTERS |
| | SHALL BE AT LEAST 1 INCH IN HEIGHT. KEYED LOCK TO BE |
| | EQUIPPED WITH AN ?OPEN/LOCKED? INDICATOR WINDOW (SUCH |
| | AS ADAMS RITE 4089 OR SIMILAR). A THUMB TURN STYLE LOCK |
| | IS NOT PERMITTED TO BE SUBSTITUTED FOR A KEYED LOCK. |
| | |
| | 6) TWO MEANS OF EGRESS IS REQUIRED, HOWEVER ASSEMBLY |
| | MAY NOT EGRESS THROUGH A HIGHER HAZARD AREA |
| | (F-2/INDUSTRIAL). PLEASE REVIEW AND PROVIDE A 2ND MEANS |
| | OF EGRESS FOR THE ASSEMBLY OCCUPANCY OF THE BUILDING. |
| | |
| | 7) ADDITIONAL EXIT AND EXIT DIRECTIONAL SIGNAGE MAY BE |
| | REQUIRED. THIS WILL BE VERIFIED IN THE FIELD. |
| | |
| | 8) PLEASE PROVIDE THE MANUFACTURER'S SPECIFICATION |
| | SHEETS FOR ALL OF THE EQUIPMENT THAT WILL BE HOUSED AND |
| | UTILIZED IN THE F-2 OCCUPANCY OF THIS LOCATION TO |
| | BETTER DETERMINE CLASSIFICATION OF HAZARD OF CONTENTS. |
| | PLEASE LABEL LOCATION OF EACH TYPE OF EQUIPMENT ON THE |
| | LIFE SAFETY SHEET OR A SEPARATE EQUIPMENT LAYOUT SHEET. |
| | |
| | 9) PLEASE INCLUDE A NARRATIVE EXPLAINING THE BREWING |
| | PROCESS AND ORDER OF OPERATIONS. |
| | |
| | ADDITIONAL COMMENTS MAY BE PROVIDED AFTER RECEIPT AND |
| | REVIEW OF RESUBMISSION. |
| | |
| | |