| 2018-03-16 15:30:57 | MECHANICAL PLAN REVIEW FAIL | | | | | | NEED RETURN AIR IN BEDROOM 1 | | | | | | 1 - 601.6 BALANCED RETURN AIR. | | | RESTRICTED RETURN AIR OCCURS IN BUILDINGS WHEN RETURNS | | | ARE LOCATED IN CENTRAL ZONES AND CLOSED INTERIOR DOORS | | | IMPEDE AIR FLOW TO THE RETURN GRILL OR WHEN CEILING | | | SPACES ARE USED AS RETURN PLENUMS AND FIRE WALLS | | | RESTRICT AIR MOVEMENT FROM ONE PORTION OF THE RETURN | | | PLENUM TO ANOTHER. PROVISIONS SHALL BE MADE IN BOTH | | | RESIDENTIAL AND COMMERCIAL BUILDINGS TO AVOID | | | UNBALANCED AIR FLOWS AND PRESSURE DIFFERENTIALS CAUSED | | | BY RESTRICTED RETURN AIR.. |
|