| 2018-03-12 09:11:31 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. NOTE # 9 STATES THAT RECEPTACLES SHALL BE TAMPER |
| | RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT |
| | APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE |
| | CORRECTION. NEC 406.12; FBC RE E4002.14 |
| | 2. THERE IS A CONFLICT WITH THE PANEL SCHEDULE/RISER |
| | DIAGRAM AND THE PLAN IN RELATION TO THE SERVICE. RISER |
| | AND PANEL SCHEDULE CALL FOR A 300 AMP SERVICE, WHILE |
| | THE PLAN SHOWS A 200 AMP SERVICE. PROVIDE CORRECTION. |
| | FBC 107.2.1 |
| | 3. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL |
| | LOADS. LOAD CALCULATION PROVIDED DOES NOT SHOW THE 2ND |
| | A/C SYSTEM, AND THE MATH IS WRONG. ALSO, DEMAND FACTORS |
| | ARE NOT APPLIED PROPERLY. NEC 220.82; FBC RE E E3602.2 |
| | 4. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC |
| | 210.8(D); FBC RE E3902.10 |
| | 5. PLAN STATES THAT AFCI PROTECTION SHOULD BE INSTALLED |
| | PER NEC 210.12(B), WHICH IS FOR CIRCUIT EXTENSIONS AND |
| | MODIFICATIONS. THIS IS A NEW DWELLING UNIT, THEREFORE, |
| | THIS CODE SECTION DOES NOT APPLY. CODE REQUIRES: |
| | ?BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, |
| | 15- AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY |
| | ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, |
| | DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, |
| | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS |
| | SHALL BE AFCI PROTECTED.? PROVIDE CORRECTION. NEC |
| | 210.12(A); FBC RE E3902.16 |
| | 6. RISER SHOWS (3) 4/0 AND (1) 2/0 WIRE FOR 300 AMP |
| | SERVICE. THIS WIRE SIZE IS NOT RATED FOR A 300 AMP |
| | SERVICE. ALSO, WHY IS THERE THREE HOT WIRES AND A |
| | NEUTRAL IF THIS IS A SINGLE PHASE SERVICE? CLARIFY |
| | AND/OR CORRECT. NEC 310.15(B)(7) AND (B)(15); FBC RE |
| | E3603.1, E3705.1 |
| | 7. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3 |
| | 8. SERVICE GROUNDING ELECTRODE TO BE AUGMENTED BY AN |
| | ADDITIONAL ELECTRODE AT LEAST 6 FEET AWAY OR PROVIDE |
| | EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR LESS. |
| | NEC 250.56; FBC RE E3608.4 |
| | 9. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C |
| | EQUIPMENT PER CODE. NEC 210.63; FBC RE E3901.12 |
| | 10. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING |
| | REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE |
| | INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG |
| | THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET |
| | FROM A RECEPTACLE OUTLET, EXCEPT FOR KITCHEN AREA WHICH |
| | REQUIRES THAT RECEPTACLE OUTLETS SHALL BE INSTALLED SO |
| | THAT NO POINT ALONG THE WALL LINE IS MORE THAN 24 |
| | INCHES MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET |
| | IN THAT SPACE. PROVIDE CORRECTION. NEC 210.52; FBC RE |
| | E3901.2.1, E3901.4 |
| | 11. A GFCI PROTECTED OUTLET ON A 20 AMP CIRCUIT IS |
| | REQUIRED WITHIN 3 FEET OF EACH BASIN. PROVIDE |
| | CORRECTION FOR MASTER BATH. NEC 210.11(C)(3), |
| | 210.52(D); FBC RE E3703.4, E3901.6 |
| | 12. PLAN SHOWS STANDARD RECESS LIGHTS IN MASTER CLOSET. |
| | PER CODE: "LIGHTING WITH OPEN OR PARTIALLY ENCLOSED |
| | LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT |
| | BE PERMITTED IN CLOTHES CLOSETS". PROVIDE CORRECTION. |
| | NEC 410.16; FBC RE E4003.12 |
| | 13. FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED |
| | GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL |
| | SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON |
| | THE EXTERIOR SIDE OF OUTDOOR ENTRANCES/EXITS WITH GRADE |
| | LEVEL ACCESS. PROVIDE CORRECTION FOR STORAGE AREA. NEC |
| | 210.70(A)(2)(B), FBC RE E3903.3 |
| | 14. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR |
| | EACH PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10 |
| | 15. PROVIDE AIC RATING OF SERVICE PANEL. NEC 110.3, |
| | 110.9 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |
| | |