| Plan Review Notes For Permit 18021186 |
| Permit Number |
18021186 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2019-01-14 10:39:30 | 3RD REVIEW FBC-2017 MECHANICAL | | | PERMIT #18021186 | | | 1/14/19 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE OUTDOOR AIR OPENING ON THE WEST SIDE OF THE | | | BUILDING MUST BE RELOCATED BECAUSE IT IS WITHIN THE | | | REQUIRED 10' MINIMUM CLEARANCE TO THE VEHICLE DRIVE AND | | | PARKING AREA- SECTION 401.4 FBC M. | | | | | | 2) PLEASE IDENTIFY THE COVERED PARKING AREA AS EITHER A | | | GARAGE ON CARPORT. PLEASE NOTE THAT PRIVATE GARAGES AND | | | CARPORTS ARE CLASSIFED AS U OCCUPANCIES AND SHALL HAVE | | | FIRE SEPARATION FROM S-1 OCCUPANCIES. PLEASE SEE | | | SECTION 406.3.1 AND TABLE 602 FBC B. | | | | | | 3) AS PREVIOUSLY REQUESTED PLEASE SUBMIT A FL. PRODUCT | | | APPROVAL AND/OR MIAMI-DADE NOA FOR THE LOUVER. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|