| 2019-01-29 16:37:39 | ****CORRECTIONS**** |
| | |
| | PETER E VALENTI |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6673 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | FBC 107. PLEASE PROVIDE MORE INFORMATION: |
| | |
| | 1A OK |
| | 1B OK |
| | |
| | 1C (FBC B 505.2.1), (PAGES LS-1, A-1, S-1,& E-1) THE |
| | SECOND FLOOR STILL DOES NOT MEET THE CRITERIA OF A |
| | MEZZANINE. WE MAY BE ABLE TO LABEL THE SECOND FLOOR AS |
| | A MEZZANINE IF THE WALL SEPERATING THE EXISTING |
| | BUILDING FROM THE PROPOSED NEW SECTION HAS AN OPENING |
| | (LARGER THAN THE DOORWAY) TO CLEARLY COMBINE THE TWO |
| | AREAS AS ONE. |
| | |
| | 2. OK |
| | 3. & 4. OK THE STRUCTURE AT THE FRONT ENTRY AREA DOES |
| | NOT EXIST, PER THE CONTRACTOR AND THE STRUCTURE AT THE |
| | ADJACENT LOT TO THE WEST IS TO BE REMOVED THROUGH THE |
| | DEMO PERMIT # 18111011. |
| | |
| | 5A & 5C (FBC B 107.3.5(4)/FBC B 704/FBC B 705), (PAGES |
| | A-1 & S-1) SPECIFIC DETAILS ARE NEEDED (AN APPROVED |
| | ASSEMBLY) ON HOW THE THREE HOUR FIRE RATING WILL BE |
| | ACHIEVED AT THE 8" CMU WALL. |
| | |
| | 5B OK |
| | |
| | 6. (FBC B 505.2.1), (PAGES LS-1, A-1, S-1 & E-1) SAME |
| | AS ITEM 1C (MEZZANINE). |
| | |
| | 7. (FBC B 1014) (PAGE A-1) PROVIDE A DETAIL FOR THE |
| | HAND RAIL IN ADDITION TO THE GUARD RAIL FOR THE STAIRS. |
| | |
| | 8, 9, 10, 11, 12, 13, & 14. OK |
| | |
| | 15. COUNTY IMPACT FEES, TO BE PAID PRIOR TO COMPLETE |
| | PERMIT APPROVAL. |
| | |
| | 16. OK |
| | |
| | 17. MISSING THE RESIDENT INSPECTOR FORM. |
| | |
| | |