| 2018-03-01 11:24:02 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THE PROPOSED PROJECT INDICATES THE USE OF FLEX DROP | | | PIPING. THE EXISTING SYSTEM APPEARS TO A TYPICAL ARM | | | OVER. | | | THERE IS NO HYDRAULIC CALCULATION SUBMITTED THAT SHOWS | | | THAT THE NEW FLEX DROPS WILL BE SUPPORTED BY THE | | | EXISTING SYSTEM DESIGN. | | | | | | PLEASE PROVIDE CALCULATIONS DETAILS. | | | | | | | | | 2) THERE ARE NO SPEC SHEETS FOR THE TYPE AND/OR SIZE OF | | | THE FLEX DROP SPRINKLERS. | | | | | | PLEASE PROVIDE SHEETS THAT MATCH THE NEW HYDRAULIC | | | CALCULATIONS. | | | | | | | | | | | | 3) THERE IS NO CEILING GRID DETAIL OR SPEC SHEETS THAT | | | WILL SUPPORT THE NEW FLEX DROPS. THE DRAWING IS VERY | | | LIMITED WITH NO SPEC SHEET BACKUP. | | | | | | PLEASE PROVIDE GREATER DETAIL AND SPEC SHEETS FOR THE | | | BRACKET AND GRID. | | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|