| 2018-03-06 08:32:30 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. LOAD CALCULATION PROVIDED CONFLICTS WITH PLAN |
| | PROVIDED. PLAN SHOWS EACH TRAILER HAS 2 PANELS, ONE |
| | DRAWING AROUND 75 AMPS AND THE OTHER DRAWING AROUND 67 |
| | AMPS. FOR A TOTAL OF 4 TRAILERS, THIS WOULD BE AROUND |
| | 568 AMPS. PROVIDE ACCURATE LOAD CALCULATION. NEC 220 |
| | 2. RISER DIAGRAM CONFLICTS WITH STATEMENT ON LOAD |
| | CALCULATION. LOAD CALCULATION STATES THAT THERE WILL BE |
| | FOUR DOUBLEWIDE TRAILERS, THE RISER DIAGRAM SHOWS |
| | CONNECTIONS TO 6 TRAILERS. CLARIFY AND/OR CORRECT. FBC |
| | 107.2.1; NEC 215.5, 215.2 |
| | 3. IT APPEARS THAT THE DESIGN WITH TWO 200 AMP PANELS |
| | FEEDING THE TRAILERS WILL OVERLOAD THE 200 AMP PANELS. |
| | PROVIDE CORRECTION. NEC 408.30 |
| | 4. PROVIDE THE REQUIRED SERVICE AREA RECEPTACLE PER |
| | CODE. NEC 210.64 |
| | 5. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. SHOW ON PLAN. NEC 250.94 |
| | 6. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10 |
| | 7. PROVIDE AIC RATING OF SERVICE DISCONNECTS AND |
| | PANELS. NEC 110.3, 110.9 |
| | 8. ALL SHEETS SUBMITTED SHOULD BE SIGNED BY THE DESIGN |
| | PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. |
| | FBC 107.1; FS 471, 481 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |