| 2018-08-29 17:48:36 | |
| | ********NOTE***** |
| | *****REVIEW IN PROGRESS......... |
| | |
| | |
| | 8- ENERGY CALCULATIONS SUBMITTED: |
| | |
| | |
| | *****REVIEW IN PROGRESS.... |
| | |
| | |
| | E) HEATING SYSTEM INFORMATION ON ITEM #13 DOESN'T MATCH |
| | EQUIPMENT CALCULATIONS SUBMITTED. REVISE AS REQUIRED. |
| | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. . |
| | |
| | F) PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| | INCLUDING THE BUILDER'S NAME. SEC. R101.5.1.1.2 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | G) BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL |
| | (EPL) DISPLAY CARD. SEC. R405.4.3 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | H) ROOF TYPE SPECIFIED ON PAGE 2 OF 5 IS INCORRECT. SEE |
| | PLANS AND REVISE. SEC. R101.5.1.1.2 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | I) DOORS INFORMATION ON PAGE 3 OF 5 IS INCORRECT. THERE |
| | IS NOT 16'X7' INSULATED DOOR SHOWN ON PLANS. NOTE: |
| | DOORS TO BE CONSIDERED ARE ONLY THE DOORS SEPARATING |
| | THE NON-A/C AREAS FROM A/C AREAS. OVERHEAD GARAGE DOOR |
| | IS NOT CONSIDERED. REVISE AS REQUIRED. SEC. |
| | R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | J) REVISE THE WINDOWS INFORMATION ON PAGE 3 OF 5. |
| | REVISE THE WINDOWS ORIENTATION AND AREA AND OVERHANG |
| | DEPTH AND SEPARATION TO MATCH PLANS. SEC. R101.5.1.1.2 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | |
| | 9- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.001 FOR: |
| | A) FLAT ROOF NOA 0529.02 SPECIFIED ON THE TYPICAL WALL |
| | SECTION ON SHEET 2 OF 3. AND, CLEARLY MARK WHICH |
| | APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO VERIFY |
| | COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301.1 |
| | FBC-RESIDENTIAL. NOTE: IF THE SELECTED ASSEMBLY DOESN'T |
| | MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN |
| | SIGNED AND SEALED RAS 117 CALCULATIONS ARE REQUIRED. |
| | |
| | B) ENTRY DOORS THAT MEET THE DESIGN PRESSURES. FLORIDA |
| | PRODUCT APPROVAL FL15180.8 SUBMITTED DON'T MEET THE |
| | DESIGN PRESSURES. NOTE: COORDINATE WITH ITEM #2 ABOVE. |
| | |
| | C) PRECAST LINTELS AS SPECIFIED ON PLANS. |
| | |
| | 10- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 11- VALUATION DECLARED IN THE PERMIT APPLICATION SEEMS |
| | TOO LOW BASED ON ALL THE SCOPE OF WORK. REVISE AS |
| | REQUIRED BY SEC. 109.3 CITY AMENDMENTS. |
| | FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING |
| | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| | TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| | |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. |
| | |
| | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY |
| | REVIEWED DRAWINGS. DON?T STAPLE OLD DRAWINGS TO PLANS. |
| | |