| Notes |
| Date |
Text |
| 2018-03-30 10:56:13 | RESIDENTIAL (R3) ALTERATION, MECHANICAL REVIEW COMMENTS | | | CODE: FBC 6TH EDITION (2017). | | | | | | 1- SCOPE OF WORK ON SHEET 1 OF 3 SPECIFIES MECHANICAL | | | SYSTEM UPGRADE/MODIFICATION. PROVIDE COMPLETE EQUIPMENT | | | SIZING CALCULATIONS (NOT JUST THE PROJECT SUMMARY) | | | SHOWING COMPLIANCE WITH SEC. R403.7.1 FBC-ENERGY | | | CONSERVATION, INCLUDING THE EQUIPMENT MANUFACTURER AND | | | MODEL NUMBER. | | | | | | 2- PROVIDE COMPLETE A/C PLAN SHOWING THE PROPOSED | | | EQUIPMENT MANUFACTURER AND MODEL AND ANY NEW DUCTWORK. | | | SEC. 107.3.5.3(10) CITY AMENDMENTS. | | | | | | | | | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | | COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. | | | | | | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD | | | DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY | | | REVIEWED DRAWINGS. DON?T STAPLE OLD DRAWINGS TO PLANS. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|