2018-03-29 17:42:56RESIDENTIAL (R3) ADDITION/ALTERATION, BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017).
  
 1-BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL,
 ONE SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO
 PALM BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS
 WITH THE IMPACT FEE STAMP AND A COPY OF THE PAID
 RECEIPT MUST BE RETURNED TO THE CITY BUILDING
 DEPARTMENT BEFORE THE BUILDING PERMIT CAN BE ISSUED.
 FOR INFORMATION CALL PALM BEACH COUNTY IMPACT FEES AT
 (561) 233-5025.
  
 2- NEW ENTRY DOOR DESIGN PRESSURES SPECIFIED ON THE
 BUILDING OPENING SCHEDULE ON SHEET 2 OF 3 ARE TOO LOW
 FOR A BUILDING LOCATED IN EXPOSURE "D". REVISE AS
 REQUIRED. SEC. R301.1 FBC-RESIDENTIAL.
  
 3- IT LOOKS LIKE THE MASONRY WALL TO BE REMOVED IS A
 BEARING WALL. THERE ARE NO DETAILS OR SPECIFICATIONS
 SHOWING HOW THE REMAINING WALL IS GOING TO BE
 REINFORCED AT THE ENDS OF THE NEW OPENING TO SUPPORT
 EXISTING RIDGE BEAM. PROVIDE DETAILS AND SPECIFICATIONS
 SHOWING REINFORCEMENT. SEC. R301.1 FBC-RESIDENTIAL.
  
 4- PROVIDE STRUCTURAL BUCK DETAIL AND SPECIFICATIONS
 FOR NEW ENTRY DOORS. SEC. R301.1 FBC-RESIDENTIAL.
  
 5- A) PROVIDE DETAILS/SPECIFICATIONS FOR WALL
 INSULATION AT NEW EXTERIOR WALL CLOSING THE EXISTING
 PORCH AND WALL BETWEEN THE EXISTING GARAGE AND PROPOSED
 AIR CONDITIONED ENTRY FOYER AS REQUIRED BY SEC. R103.2
 FBC-ENERGY CONSERVATION. NOTE: COORDINATE R-VALUE WITH
 ENERGY CALCULATIONS.
  
 B) TYPICAL WALL SECTION ON SHEET 2 OF 3 SPECIFIES "R-30
 ISONENE FOAM INSULATION". SPECIFY THE SIZE OF EXISTING
 ROOF RAFTERS TO VERIFY THAT R-30 FOAM INSULATION WILL
 FIT BETWEEN ROOF RAFTERS AS SHOWN ON THE WALL SECTION.
 SEC. R103.2 FBC-ENERGY CONSERVATION.
 NOTE; IT LOOKS LIKE THERE IS A TYPO. DO YOU MEAN
 ICYNENE FOAM INSULATION?. PLEASE CORRECT.
  
 6- A) PROVIDE ICYNENE FOAM INSULATION ICC EVALUATION
 REPORT TO VERIFY COMPLIANCE WITH SEC. R316
 FBC-RESIDENTIAL. NOTE: COORDINATE R-VALUE WITH ITEM
 #5(B) ABOVE AND ENERGY CALCULATIONS.
  
 B) ENGINEER OF RECORD TO REVIEW AND APPROVE EVALUATION
 REPORT PRIOR TO SUBMITTAL TO THIS OFFICE., SEC.
 107.3.4.2 CITY AMENDMENTS.
  
 7- SPECIFY CARBON MONOXIDE ALARMS AS REQUIRED BY SEC.
 R315.1 FBC-RESIDENTIAL FOR ALL EXISTING BEDROOMS.
  
 8- ENERGY CALCULATIONS SUBMITTED:
 A) THE ENERGY FORM R405-2017 IS REQUIRED TO BE SIGNED
 AND DATED BY THE OWNER OR OWNER'S LEGALLY DESIGNATED
 AGENT AS REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY
 CONSERVATION, 6TH EDITION (2017).
  
 B) ITEM #1 IS INCORRECT. THIS IS NOT NEW CONSTRUCTION.
 REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 C) PROVIDE MANUFACTURER'S SPECIFICATIONS FOR EXISTING
 DOORS AND WINDOWS SHOWING THE U-FACTOR AND SHGC FACTORS
 SPECIFIED ON ITEM #7 AS REQUIRED BY SEC. R405.4.3
 FBC-ENERGY CONSERVATION.
  
 D) NEED TO PROVIDE THE INFORMATION FOR ADJACENT WALL
 BETWEEN THE EXISTING GARAGE AND NEW AIR CONDITIONED
 FOYER AREA. COMPLETE ITEM #9. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 E) HEATING SYSTEM INFORMATION ON ITEM #13 DOESN'T MATCH
 EQUIPMENT CALCULATIONS SUBMITTED. REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. .
  
 F) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING THE BUILDER'S NAME. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 G) BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD. SEC. R405.4.3 FBC-ENERGY
 CONSERVATION.
  
 H) ROOF TYPE SPECIFIED ON PAGE 2 OF 5 IS INCORRECT. SEE
 PLANS AND REVISE. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 I) DOORS INFORMATION ON PAGE 3 OF 5 IS INCORRECT. THERE
 IS NOT 16'X7' INSULATED DOOR SHOWN ON PLANS. NOTE:
 DOORS TO BE CONSIDERED ARE ONLY THE DOORS SEPARATING
 THE NON-A/C AREAS FROM A/C AREAS. OVERHEAD GARAGE DOOR
 IS NOT CONSIDERED. REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 J) REVISE THE WINDOWS INFORMATION ON PAGE 3 OF 5.
 REVISE THE WINDOWS ORIENTATION AND AREA AND OVERHANG
 DEPTH AND SEPARATION TO MATCH PLANS. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
  
 9- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) FLAT ROOF NOA 0529.02 SPECIFIED ON THE TYPICAL WALL
 SECTION ON SHEET 2 OF 3. AND, CLEARLY MARK WHICH
 APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301.1
 FBC-RESIDENTIAL. NOTE: IF THE SELECTED ASSEMBLY DOESN'T
 MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN
 SIGNED AND SEALED RAS 117 CALCULATIONS ARE REQUIRED.
  
 B) ENTRY DOORS THAT MEET THE DESIGN PRESSURES. FLORIDA
 PRODUCT APPROVAL FL15180.8 SUBMITTED DON'T MEET THE
 DESIGN PRESSURES. NOTE: COORDINATE WITH ITEM #2 ABOVE.
  
 C) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 10- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 11- VALUATION DECLARED IN THE PERMIT APPLICATION SEEMS
 TOO LOW BASED ON ALL THE SCOPE OF WORK. REVISE AS
 REQUIRED BY SEC. 109.3 CITY AMENDMENTS.
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DON?T STAPLE OLD DRAWINGS TO PLANS.
  