| 2018-03-16 13:36:22 | RESIDENTIAL (R3) REVISION, PLUMBING REVIEW COMMENTS |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | 1- PLUMBING RISER DIAGRAM SUBMITTED SHOWS 2 WET VENTED |
| | FIXTURES DRAINS DISCHARGING UPSTREAM OF THE DRY VENTED |
| | FIXTURE DRAIN CONNECTION. REVISE AS REQUIRED. |
| | |
| | SEC. P3108.2.1 FBC-RESIDENTIAL. HORIZONTAL WET VENT. |
| | THE DRY-VENT CONNECTION FOR A HORIZONTAL WET-VENT |
| | SYSTEM SHALL BE AN INDIVIDUAL VENT OR A COMMON VENT FOR |
| | ANY BATHROOM GROUP FIXTURE, EXCEPT AN EMERGENCY FLOOR |
| | DRAIN. WHERE THE DRY VENT CONNECTS TO A WATER CLOSET |
| | FIXTURE DRAIN, THE DRAIN SHALL CONNECT HORIZONTALLY TO |
| | THE HORIZONTAL WET VENT SYSTEM. NOT MORE THAN ONE |
| | WET-VENTED FIXTURE DRAIN SHALL DISCHARGE UPSTREAM OF |
| | THE DRY-VENTED FIXTURE DRAIN CONNECTION |
| | |
| | 2- REVISE THE DRAIN PIPE SIZE FOR ALL LAVATORIES AND |
| | KITCHEN SINKS SHOWN IN THE RISER DIAGRAM TO COMPLY WITH |
| | TABLE P3201.7 FBC-RESIDENTIAL. |
| | |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. |
| | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY |
| | REVIEWED DRAWINGS. DON'T STAPLE OLD DRAWINGS TO PLANS. |
| | |
| | |