Plan Review Notes
Plan Review Notes For Permit 18021075
Permit Number 18021075
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2018-02-28 13:28:05 
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) ON REVIEW OF THE LOCATION OF THE DDCV IT DOES NOT
 APPEAR TO COMPLY WITH THE REQUIRMENTS OF NFPA 24.
  
 A REVIEW OF THE MASTER PERMIT, 17010799, SHEET FP 1 OF
 1, INDICATES THAT THE UNDERGROUND WORK SHALL COMPLY
 WITH NFPA 24.
  
 PER NFPA 24, CHAPTER 6, VALVES
  
  
 6.2.11 ALL CONNECTIONS TO PRIVATE FIRE SERVICE MAINS
 FOR FIRE
 PROTECTION SYSTEMS SHALL BE ARRANGED IN ACCORDANCE WITH
 ONE
 OF THE FOLLOWING SO THAT THEY CAN BE ISOLATED:
 (1)*A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40
 FT (12 M)
 FROM THE BUILDING
 (A) FOR BUILDINGS LESS THAN 40 FT (12 M) IN HEIGHT, A
 POST
 INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED
 CLOSER THAN 40 FT (12 M) BUT AT LEAST AS FAR FROM THE
 BUILDING AS THE HEIGHT OF THE WALL FACING THE POST
 INDICATOR
 VALVE.
 (2) A WALL POST INDICATOR VALVE
 (3) AN INDICATING VALVE IN A PIT, INSTALLED IN
 ACCORDANCE WITH
 SECTION 6.4
 (4)*A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING
 VALVE NOT
 LESS THAN 40 FT (12 M) FROM THE BUILDING
 (A) FOR BUILDINGS LESS THAN 40 FT (12 M) IN HEIGHT, A
 BACKFLOW
 PREVENTER WITH AT LEAST ONE INDICATING VALVE SHALL
 BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FT (12 M)
 BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF
 THE WALL FACING THE BACKFLOW PREVENTER.
 (5)*A NONINDICATING VALVE, SUCH AS AN UNDERGROUND GATE
 VALVE
 WITH AN APPROVED ROADWAY BOX, COMPLETE WITH T-WRENCH,
 LOCATED NOT LESS THAN 40 FT (12 M) FROM THE BUILDING
 (A) FOR BUILDINGS LESS THAN 40 FT (12 M) IN HEIGHT, A
 NONINDICATING
 VALVE, SUCH AS AN UNDERGROUND GATE VALVE WITH AN
 APPROVED ROADWAY BOX, COMPLETE WITH T-WRENCH, SHALL
 BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FT (12 M)
 BUT
 AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF THE
 WALL
 FACING THE BACKFLOW PREVENTER.
 (6) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM
 ACCESSIBLE
 FROM THE EXTERIOR
 (7) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE
 ACCESSIBLE
 FROM THE EXTERIOR AS PERMITTED BY THE AUTHORITY HAVING
 JURISDICTION.
  
 6.5 BACKFLOW PREVENTION ASSEMBLIES.
 6.5.1 WHERE USED IN ACCORDANCE WITH 6.2.11(4), BACKFLOW
 PREVENTION
 ASSEMBLIES SHALL BE INSTALLED IN ACCORDANCE WITH THEIR
 INSTALLATION INSTRUCTIONS.
 6.5.2 WHERE BACKFLOW PREVENTION ASSEMBLIES ARE USED,
 THEY
 SHALL BE PROTECTED AGAINST MECHANICAL DAMAGE WHERE
 NEEDED.
  
 THE LOCATION OF THE DDCV APPEARS TO BE CLOSER THAN THE
 HEIGHT OF THE WALL.
  
 PLEASE PROVIDE AN ALTERNATE LOCATION OR PROVIDE
 PROTECTION SHOULD THE WALL COLLASPE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  