| 2018-10-04 16:59:26 | RESIDENTIAL (R2) ALTERATION, FOURTH BUILDING REVIEW |
| | CHECKLIST. |
| | CODE: FBC 6TH EDITION (2017). |
| | |
| | 1) THE OWNER OR OWNER'S LEGALLY AUTHORIZED AGENT NEED |
| | TO CERTIFY AT THE BOTTOM OF THE ENERGY CALCULATIONS |
| | PRIOR TO RECEIVING THE PERMIT AS REQUIRED BY SEC. |
| | R103.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | 2) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| | FLOOR/CEILING ASSEMBLY FOR TENANT SEPARATION WITH THE |
| | APT ON THE SECOND FLOOR. NOTE: TENANT SEPARATION WALL |
| | DETAIL "F" ON SHEET S1A DOESN'T PROVIDE SPECIFICATIONS |
| | FOR APPROVED HORIZONTAL ASSEMBLY. IT ONLY SPECIFIES THE |
| | WALL ASSEMBLY UL-U311. PROVIDE COMPLETE DETAILS AND |
| | SPECIFICATIONS FOR APPROVED HORIZONTAL FIRE RATED |
| | ASSEMBLY AS REQUIRED . SEC. 420.3 FBC. |
| | |
| | RESPONSE: |
| | NEW DETAIL "G" ON SHEET S1A: |
| | A) THE TIME ASSIGNED FOR WOOD JOISTS IS 10 MINUTES NOT |
| | 20 MINUTES. SEE TABLE 722.6.2(2). REVISE AS REQUIRED. |
| | NOTE: KEEP IN MIND THAT NEED TO GET 1 HOUR FIRE RATED |
| | HORIZONTAL ASSEMBLY. NEED TO REVISE ASSEMBLY TO MEET |
| | THE ONE HOUR FIRE RATING. |
| | |
| | B) PROVIDE COMPLETE SPECIFICATIONS FOR THE FLOOR |
| | ASSEMBLY SUB FLOORING AND FINISH FLOOR AS REQUIRED BY |
| | SEC. 722.6.2.4. FBC. |
| | |
| | C) PROVIDE COMPLETE SPECIFICATIONS FOR THE ADDITIONAL |
| | PROTECTION OF THE FLOOR ASSEMBLY AS REQUIRED BY SEC. |
| | 722.6.2.4. FBC. |
| | |
| | D) PROVIDE COMPLETE SPECIFICATIONS FOR THE FASTENING OF |
| | THE FLOOR ASSEMBLY FRAMING MEMBERS AND MEMBRANES |
| | (PLYWOOD, GYPSUM BOARD ETC) AS REQUIRED BY SEC. |
| | 722.6.2.6 FBC. |
| | |
| | E) THERE IS A FIRE NOTE ABOVE NEW DETAIL "G" THAT |
| | SPECIFIES 2 LAYERS OF 1/2" TYPE X GYPSUM BOARD. |
| | COORDINATE THIS INFORMATION WITH DETAIL G AND ALL WALL |
| | SECTIONS TO AVOID CONFUSION/DISCREPANCIES. SEC. 107.2.1 |
| | CITY AMENDMENTS. |
| | |
| | 3) INFORMATION ON DRAWINGS NEED TO BE COORDINATED. |
| | INFORMATION ON TENANT SEPARATION HORIZONTAL ASSEMBLY |
| | DETAIL "G" NEEDS TO BE COORDINATED WITH CEILING |
| | INFORMATION ON ALL WALL SECTION DETAILS SHOWN ON SHEET |
| | S1 AND SHEET S1A. REVISE AS REQUIRED TO MATCH. SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | |
| | 4) CEILING INFORMATION UNDER THE EXISTING STAIRS DETAIL |
| | ON SHEET S1 WAS REVISED. PREVIOUS DETAIL SPECIFIED 2 |
| | LAYERS OF 5/8" FIRE RATED GYPSUM BOARD. NEW DETAIL |
| | SPECIFIES ONLY ONE LAYER. CLARIFY/REVISE AS REQUIRED. |
| | NEED TO PROVIDE ONE HOUR FIRE RATED TENANT SEPARATION |
| | ASSEMBLY WITH THE ABOVE UNIT. SEC. 420.3 FBC. |
| | COORDINATE WITH ITEM #2 ABOVE. |
| | |
| | 5) ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, |
| | AND SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING AS REQUIRED BY SEC. |
| | 801.3 FBC-EXISTING BUILDING. SHOW COMPLIANCE WITH THE |
| | SOUND TRANSMISSION FOR FLOOR/CEILING ASSEMBLY. |
| | FLOORING UNDERLAYMENT |
| | SOUND INSULATION MATERIAL: |
| | A) PROVIDE 2 COPIES OF THE FLAME SPREAD INDEX AND SMOKE |
| | DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 6TH EDITION |
| | (2017). |
| | |
| | B) PROVIDE 2 COPIES OF THE SOUND TRANSMISSION CLASS |
| | (STC) TEST DONE IN ACCORDANCE WITH ASTM E 90 AS |
| | REQUIRED BY SEC. 1207.2 OF FBC 6TH EDITION (2017). |
| | |
| | C) PROVIDE 2 COPIES OF THE IMPACT INSULATION CLASS |
| | (IIC) TEST DONE IN ACCORDANCE WITH ASTM E 492 AS |
| | REQUIRED BY SEC. 1207.3 OF FBC 6TH EDITION (2017). |
| | |
| | RESPONSE: |
| | ICC EVALUATION REPORT ESR-2540 SUBMITTED IS FOR 2X10 |
| | WOOD JOIST FLOOR ASSEMBLIES. THIS DOESN'T MATCH |
| | EXISTING FLOOR FRAMING. PROVIDE COMPLIANCE WITH THE |
| | ABOVE A, B AND C SOUND INSULATION REQUIREMENTS. |
| | NOTE: COORDINATE WITH HORIZONTAL TENANT ASSEMBLY DETAIL |
| | G TO AVOID CONFLICTS/DELAYS. |
| | |
| | |
| | 6) PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.001 FOR: |
| | NOTE: THIS MAY BE SUBMITTED LATER AS DEFERRED |
| | SUBMITTAL, BUT BEFORE INSTALLATION (NO FEES). |
| | |
| | A) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY |
| | IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE |
| | DESIGN PRESSURES OF SEC. 1609 FBC. NOTE: IF THE |
| | SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES FOR |
| | ALL ROOF ZONES, THEN SIGNED AND SEALED RAS 117 |
| | CALCULATIONS ARE REQUIRED. |
| | |
| | RESPONSE: |
| | NO PRODUCT APPROVAL WAS SUBMITTED. NEED PRODUCT |
| | APPROVAL AND SPECIFIC ASSEMBLY TO BE INSTALLED. |
| | |
| | B) ROOF TILE ADHESIVE REFERENCED IN ROOF TILE NOA |
| | 15-0915.09 SUBMITTED. ROOF TILE ADHESIVE RTA-1 |
| | SUBMITTED IS NOT THE ONE REFERENCED IN THE NOA FOR CLAY |
| | TILE. AND, CLEARLY MARK PADDY SIZE. |
| | |
| | 7- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 8) PROVIDE COMPLETE INFORMATION FOR THE FIRE RATING |
| | ASSEMBLY BELOW THE STAIRS AND BY THE PANTRY CLOSET ON |
| | FIRST FLOOR KITCHEN. SEC. 420.2 AND 420.3 FBC. |
| | |
| | RESPONSE: |
| | SPECIFIED ASSEMBLY DOESN'T PROVIDE 1 HOUR FIRE RATED |
| | ASSEMBLY. COORDINATE WITH ITEM #4 ABOVE. |
| | |
| | |
| | ARCHITECTS-ENGINEERS |
| | FLORIDA STATUTE 553.80(2)(B): |
| | WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW |
| | |
| | NOTE: |
| | ENGINEER OF RECORD TO PROVIDE RESPONSE LETTER |
| | ADDRESSING EACH COMMENT TO AVOID PLAN REVIEW FEES AS |
| | REQUIRED BY FLORIDA STATUTE 553.80(2)(B). |
| | |
| | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY |
| | REVIEWED DRAWINGS. DON'T STAPLE OLD DRAWINGS TO PLANS. |
| | |