| 2018-07-17 07:45:28 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL |
| | LOADS. ALL LOADS SUPPLIED ARE THE SAME FOR EACH PANEL |
| | EVEN THOUGH THERE ARE DIFFERENCES IN EACH UNIT. ALSO, |
| | THE PANEL SCHEDULE SHOWS 10 KW HEAT FOR THE AHU, BUT |
| | YOU HAVE INCLUDED 3.25 KW IN LOAD CALCULATION. THERE |
| | SHOULD BE ONE LOAD CALCULATION FOR ENTIRE SERVICE, AND |
| | THEN A LOAD CALCULATION FOR EACH SUB-PANEL ALSO. NEC |
| | 220 (LOAD CALCULATION PROVIDED IS NOT CODE COMPLIANT. |
| | DEMAND FACTORS HAVE BEEN APPLIED TO EACH PANEL, AND |
| | THEN AGAIN BASED ON 220.84. THAT CODE SECTION EXPLAINS |
| | THAT THE LOADS ARE ALL ADDED TOGETHER AND THEN A DEMAND |
| | FACTOR IS APPLIED ONE TIME. PROVIDE ACCURATE LOAD |
| | CALCULATION.) |
| | 2. PROVIDE ACCURATE RISER DIAGRAM, SHOWING ALL DETAILS |
| | OF SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, |
| | WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY |
| | SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW |
| | INTERSYSTEM BONDING TERMINATION POINT. PLAN CURRENTLY |
| | SHOWS DISCONNECT A FEEDING NOTHING, DISCONNECT B |
| | FEEDING PANEL A, AND DISCONNECT C FEEDING PANEL B. ALSO |
| | NEED TO SHOW WIRE SIZE FOR SERVICE LATERAL. PROVIDE |
| | CORRECTIONS. NEC 215.5, 230, 250.50, 250.94, 408.30 |
| | (THIS IS MOSTLY CORRECTED, BUT SHOWS A 130 AMP BREAKER |
| | FEEDING APARTMENT 3. THIS IS NOT A STANDARD FUSE SIZE |
| | PER 240.6. PROVIDE CORRECTION.) |
| | 3. CORRECTED. |
| | 4. PLAN SHOWS AFCI COVERAGE FOR SOME RECEPTACLE OUTLETS |
| | BUT NOT LIGHTING. THIS COVERAGE IS NOT TO CODE AND NOT |
| | COMPLETE. CODE REQUIRES: "BRANCH CIRCUITS THAT SUPPLY |
| | 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS |
| | INSTALLED IN KITCHENS, FAMILY ROOMS, DINING ROOMS, |
| | LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, |
| | SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, HALLWAYS, |
| | LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS SHALL BE AFCI |
| | PROTECTED." PROVIDE CORRECTION. NEC 210.12 (NOTE |
| | PROVIDED FOR THIS IS IN CONFLICT WITH THE ABOVE |
| | STATEMENT. SOME AREAS WILL REQUIRE BOTH AFCI AND GFCI |
| | PROTECTION. THIS SHOULD ALSO BE REFLECTED IN PANEL |
| | SCHEDULE.) |
| | 5. CORRECTED. |
| | 6. PROVIDE ACCURATE PANEL SCHEDULES, THE WIRE AND |
| | BREAKER SIZE FOR THESE CIRCUITS, AND AFCI OR GFCI |
| | PROTECTION WHERE APPLICABLE TO COMPLY WITH CODE. ALL |
| | PANEL SCHEDULES PROVIDED ARE IDENTICAL EVEN THOUGH THE |
| | UNITS ARE DIFFERENT. CIRCUITS SHOULD HAVE UNIQUE |
| | IDENTIFICATION. NEC 210.8, 210.12, 215.5, 408.4 (AFCI |
| | PROTECTION NOT LISTED COMPLETELY.) |
| | 7. CORRECTED. |
| | 8. CORRECTED. |
| | 9. CORRECTED. |
| | |
| | NEW COMMENT: |
| | |
| | 10. BE ADVISED THAT SOME OF THESE COMMENTS HAVE NOT |
| | BEEN ADDRESSED FOR TWO REVIEWS. IF UPON THE THIRD |
| | REVIEW, IF IT IS NECESSARY TO REJECT THE SUBMITTED PLAN |
| | A THIRD TIME FOR THE SAME REASONS, AN ADDITIONAL PLAN |
| | REVIEW IS REQUIRED. FLORIDA STATUTES STATE: WITH |
| | RESPECT TO EVALUATION OF DESIGN PROFESSIONALS |
| | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)? |
| | (PLAN REVIEW FEE ADDED.) |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |