| Plan Review Notes For Permit 18021046 |
| Permit Number |
18021046 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-04-25 13:15:50 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) SHEET S 1A - CALL-OUT DRAWING INDICATED AS DIAMOND G | | | DOES NOT SHOW TYPE X DRYWALL ON THE CEILING. ALL | | | CEILING AREAS SHALL BE TYPE X AS INDICATED IN CALL-OUT | | | DRAWING DIAMOND F. | | | | | | PLEASE ENSURE ALL CEILING AREAS HAVE 1 HOUR FIRE RATED | | | CONSTRUCTION FEATURES. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|