| Plan Review Notes For Permit 18021046 |
| Permit Number |
18021046 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-03-16 11:40:13 | 1- FLAT ROOF NOA 15-1020.01 SUBMITTED: CLEARLY MARK | | | WHICH APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO | | | VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. | | | 1609 FBC-BUILDING. IF THE SELECTED ASSEMBLY DOESN'T | | | MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN | | | SIGNED AND SEALED RAS 117 CALCULATIONS ARE REQUIRED. | | | RAS 117 CALCULATIONS ARE REQUIRED TO HAVE THE FLORIDA | | | ENGINEER'S SEAL AND ORIGINAL HANDWRITTEN SIGNATURE, | | | COPIES OR OTHER FACSIMILES ARE NOT ACCEPTABLE. FAC | | | 61G15 - 23.002 DIGITAL SIGNATURES ARE ONLY ACCEPTABLE | | | FOR ELECTRONICALLY TRANSMITTED PLANS AND DOCUMENTS. | | | | | | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | FAC 61G20-3.001 FOR: | | | A) ROOF TILE ADHESIVE IF SPECIFIED BY THE DESIGNER OF | | | RECORD. AND SPECIFY PADDY SIZE. SEE ROOF TILE PRODUCT | | | APPROVAL FOR LISTED ADHESIVES. | | | | | | | | | APPROVED: | | | 1) ENTEGRA ROOF TILE NOA 16-0112.08 | | | |
|