| 2018-03-14 08:45:19 | 1ST REVIEW: FBC 2017 6TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. PROVIDE WATER ISOMETRIC SHOW EXISTING AND NEW. PER | | | WPB AMEND TO FBC 107.3.5.1.3(13) | | | | | | 2. THE SOIL STACK FOR 2ND FLOOR IS NOT SHOWN ON 1ST | | | FLOOR ISOMETRIC, THE LAUNDRY IS NOT SHOWN ON 2ND FLOOR | | | ISOMETRIC SHOW ALL NEW AND EXISTING PIPING AND MARK IT | | | AS EXISTING OR NEW. PER WPB AMEND TO FBC | | | 107.3.5.1.3(13) | | | | | | 3. BACKFLOW REQUIRED ON WATER SERVICE SHOW ON WATER | | | ISOMETRIC NEW OR EXISTING. PER WPB UTILITIES DEPARTMENT | | | CROSS CONNECTION MANUAL | | | | | | 4. THE COVER SHEET UNDER SCOPE OF WORK LISTED AS A | | | SINGLE FAMILY HOME THIS DRELLING IS AN R2 OCCUPANCY PER | | | FBC 310.4 PLEASE CLARIFY. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|