| 2018-03-20 09:15:17 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET CVR - THE PROPOSED PROJECT CHANGES A DUPLEX |
| | INTO A TRIPLEX CREATING A NEW APARTMENT BUILDING. |
| | |
| | PER NFPA 101, CHAPTER 3, DEFINITIONS |
| | |
| | 3.3.36.3* APARTMENT BUILDING. A BUILDING OR PORTION |
| | THEREOF |
| | CONTAINING THREE OR MORE DWELLING UNITS WITH |
| | INDEPENDENT |
| | COOKING AND BATHROOM FACILITIES. (SAF-RES) |
| | |
| | PLEASE CORRECT. |
| | |
| | |
| | 2) SHEET CVR - THERE IS NO APPLICABLE REFERNECED FIRE |
| | CODE. |
| | |
| | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| | 6TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING |
| | THE 2015 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER |
| | APPLICABLE CODES OR STANDARDS. |
| | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 13, 2013 EDITION. |
| | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 72, 2013 EDITION. |
| | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 241, 2013 EDITION. |
| | FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 10, 2013 EDITION. |
| | ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2014 EDITION. |
| | |
| | PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT AND COMPLIANCE |
| | |
| | |
| | 3) SHEET S 1 - A FIRE SPRINKLER SYSTEM IS REQUIRED. |
| | |
| | PER NFPA 101, CHAPTER 30, NEW APARTMENT BUILDINGS. |
| | |
| | 30.3.5 EXTINGUISHMENT REQUIREMENTS. |
| | 30.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY |
| | AN APPROVED, |
| | SUPERVISED AUTOMATIC SPRINKLER SYSTEM INSTALLED IN |
| | ACCORDANCE WITH |
| | 30.3.5.2. |
| | 30.3.5.2 WHERE AN AUTOMATIC SPRINKLER SYSTEM IS |
| | INSTALLED, EITHER FOR |
| | TOTAL OR PARTIAL BUILDING COVERAGE, THE SYSTEM SHALL BE |
| | INSTALLED IN |
| | ACCORDANCE WITH SECTION 9.7, AS MODIFIED BY 30.3.5.3 |
| | AND 30.3.5.4. IN |
| | BUILDINGS FOUR OR FEWER STORIES ABOVE GRADE PLANE, |
| | SYSTEMS IN |
| | ACCORDANCE WITH NFPA 13R, STANDARD FOR THE INSTALLATION |
| | OF |
| | SPRINKLER SYSTEMS IN LOW-RISE RESIDENTIAL OCCUPANCIES, |
| | SHALL BE |
| | PERMITTED. |
| | |
| | PLEASE PROVIDE FOR THE REQUIREMENT AS WELL AS 61G |
| | DOCUMENTS PER FLORIDA STATUTE WITH THIS MASTER PERMIT. |
| | |
| | |
| | |
| | 4) THE FIRE SPRINKLER SYSTEM IS REQUIRED TO BE |
| | SUPERVISED AND MONITORED. |
| | |
| | PER NFPA 101, CHAPTER 9, FIRE PREOTECTIONS SYSTEMS. |
| | |
| | 9.7.2 SUPERVISION. |
| | 9.7.2.1* SUPERVISORY SIGNALS. |
| | 9.7.2.1.1 WHERE SUPERVISED AUTOMATIC SPRINKLER SYSTEMS |
| | ARE REQUIRED BY |
| | ANOTHER SECTION OF THIS CODE, SUPERVISORY ATTACHMENTS |
| | SHALL BE INSTALLED |
| | AND MONITORED FOR INTEGRITY IN ACCORDANCE WITH NFPA 72, |
| | NATIONAL FIRE |
| | ALARM AND SIGNALING CODE, AND A DISTINCTIVE SUPERVISORY |
| | SIGNAL SHALL BE |
| | PROVIDED TO INDICATE A CONDITION THAT WOULD IMPAIR THE |
| | SATISFACTORY |
| | OPERATION OF THE SPRINKLER SYSTEM. |
| | 9.7.2.1.2 SUPERVISORY SIGNALS SHALL SOUND AND SHALL BE |
| | DISPLAYED EITHER AT |
| | A LOCATION WITHIN THE PROTECTED BUILDING THAT IS |
| | CONSTANTLY ATTENDED BY |
| | QUALIFIED PERSONNEL OR AT AN APPROVED, REMOTELY LOCATED |
| | RECEIVING |
| | FACILITY. |
| | 9.7.2.2 ALARM SIGNAL TRANSMISSION. |
| | 9.7.2.2.1 WHERE SUPERVISION OF AUTOMATIC SPRINKLER |
| | SYSTEMS IS REQUIRED |
| | BY ANOTHER SECTION OF THIS CODE, WATERFLOW ALARMS SHALL |
| | BE TRANSMITTED |
| | TO AN APPROVED, PROPRIETARY ALARM-RECEIVING FACILITY, A |
| | REMOTE STATION, A |
| | CENTRAL STATION, OR THE FIRE DEPARTMENT. |
| | |
| | PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT AND COMPLIANCE |
| | AS WELL AS SHOP DRAWING SUBMITTAL. |
| | |
| | |
| | |
| | 5) SHEET S 1 - THERE ARE MULTIPLE DIAMOND SHAPED |
| | REFERNCES THAT DO NOT COINCIDE WITH ANY DRAWINGS OR |
| | SHEETS. |
| | |
| | PLEASE REVIEW AND PROVIDE THEIR DRAWING REFERENCES. |
| | |
| | |
| | |
| | 6) SHEET S 1 - THERE APPEARS TO BE 1 HOUR RATED WALLS |
| | THAT INTERSECT WITH BEARING WALLS. THE BEARING WALLS DO |
| | NOT HAVE ANY RATING INDICATED. |
| | |
| | 30.3.7 SUBDIVISIONS OF BUILDING SPACES. BUILDINGS SHALL |
| | BE |
| | SUBDIVIDED IN ACCORDANCE WITH 30.3.7.1 OR 30.3.7.2. |
| | 30.3.7.1 IN BUILDINGS NOT MEETING THE REQUIREMENT OF |
| | 30.3.7.2, |
| | DWELLING UNITS SHALL BE SEPARATED FROM EACH OTHER BY |
| | WALLS AND |
| | FLOORS CONSTRUCTED AS FIRE BARRIERS HAVING A MINIMUM |
| | 1-HOUR FIRE |
| | RESISTANCE RATING. |
| | |
| | 30.3.7.2 IN BUILDINGS PROTECTED THROUGHOUT BY AN |
| | APPROVED, |
| | SUPERVISED AUTOMATIC SPRINKLER SYSTEM, DWELLING UNITS |
| | SHALL BE |
| | SEPARATED FROM EACH OTHER BY WALLS AND FLOORS |
| | CONSTRUCTED AS FIRE |
| | BARRIERS HAVING A MINIMUM ?-HOUR FIRE RESISTANCE |
| | RATING. |
| | |
| | PLEASE REVIEW AND CORRECT WITH APPLICABLE RATED |
| | CONSTRUCTION AND LISTING. |
| | |
| | |
| | |
| | 7) SHEET S 1 - THERE IS NO INDICATION OF ANY RATING OF |
| | THE STAIRWELL EXIT ACCESS. |
| | |
| | 30.3.6 CORRIDORS. |
| | 30.3.6.1 WALLS. EXIT ACCESS CORRIDOR WALLS SHALL COMPLY |
| | WITH |
| | 30.3.6.1.1 OR 30.3.6.1.2. |
| | 30.3.6.1.1 IN BUILDINGS NOT COMPLYING WITH 30.3.6.1.2, |
| | EXIT ACCESS |
| | CORRIDOR WALLS SHALL CONSIST OF FIRE BARRIERS IN |
| | ACCORDANCE WITH |
| | SECTION 8.3 THAT HAVE NOT LESS THAN A 1-HOUR FIRE |
| | RESISTANCE RATING. |
| | 30.3.6.1.2 IN BUILDINGS PROTECTED THROUGHOUT BY AN |
| | APPROVED, |
| | SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| | WITH |
| | 30.3.5.2, CORRIDOR WALLS SHALL HAVE A MINIMUM ?-HOUR |
| | FIRE |
| | RESISTANCE RATING. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 8) SHEET S 1 - THERE ARE NO REFERNECES TO ANY RATING |
| | FOR THE CEILING/FLOOR ASSEMBLY. |
| | |
| | 30.3.7 SUBDIVISIONS OF BUILDING SPACES. BUILDINGS SHALL |
| | BE |
| | SUBDIVIDED IN ACCORDANCE WITH 30.3.7.1 OR 30.3.7.2. |
| | 30.3.7.1 IN BUILDINGS NOT MEETING THE REQUIREMENT OF |
| | 30.3.7.2, |
| | DWELLING UNITS SHALL BE SEPARATED FROM EACH OTHER BY |
| | WALLS AND |
| | FLOORS CONSTRUCTED AS FIRE BARRIERS HAVING A MINIMUM |
| | 1-HOUR FIRE |
| | RESISTANCE RATING. |
| | |
| | 30.3.7.2 IN BUILDINGS PROTECTED THROUGHOUT BY AN |
| | APPROVED, |
| | SUPERVISED AUTOMATIC SPRINKLER SYSTEM, DWELLING UNITS |
| | SHALL BE |
| | SEPARATED FROM EACH OTHER BY WALLS AND FLOORS |
| | CONSTRUCTED AS FIRE |
| | BARRIERS HAVING A MINIMUM ?-HOUR FIRE RESISTANCE |
| | RATING. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |