| 2018-03-13 11:05:10 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. WRONG CODE SPECIFIED FOR DESIGN. THE PROVISIONS OF |
| | THE FLORIDA BUILDING CODE, RESIDENTIAL SHALL APPLY TO |
| | THE CONSTRUCTION, ALTERATION, MOVEMENT, ENLARGEMENT, |
| | REPLACEMENT, REPAIR, EQUIPMENT, USE AND OCCUPANCY, |
| | LOCATION, REMOVAL AND DEMOLITION OF DETACHED ONE- AND |
| | TWO-FAMILY DWELLINGS AND TOWNHOUSES NOT MORE THAN THREE |
| | STORIES ABOVE GRADE PLANE IN HEIGHT WITH A SEPARATE |
| | MEANS OF EGRESS AND THEIR ACCESSORY STRUCTURES NOT MORE |
| | THAN THREE STORIES ABOVE GRADE PLANE IN HEIGHT. PROVIDE |
| | CORRECTION. FBC RE R101.2 |
| | 2. NOTE STATES THAT RECEPTACLES SHALL BE TAMPER |
| | RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT |
| | APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE |
| | CORRECTION. NEC 406.12; FBC RE E4002.14 |
| | 3. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| | WITH CODE. NEC 210.8, 210.12, 215.5, 408.4 |
| | 4. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC 210.8(D) |
| | 5. PROVIDE AFCI PROTECTION PER CODE: ?BRANCH CIRCUITS |
| | THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE |
| | OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS, DINING |
| | ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, |
| | BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, |
| | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS |
| | SHALL BE AFCI PROTECTED.? PROVIDE CORRECTION. NEC |
| | 210.12 |
| | 6. PROVIDE NOTE TO COMPLY WITH CODE FOR LIGHTING IN |
| | CLOSETS: "LIGHTING WITH OPEN OR PARTIALLY ENCLOSED |
| | LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT |
| | BE PERMITTED IN CLOTHES CLOSETS". NEC 410.16 |
| | 7. WILL THERE BE ANY ADDITIONAL LOADS ADDED, NEW |
| | EQUIPMENT? IF SO, PROVIDE LOAD CALCULATION, INCLUDE |
| | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| | IS ADEQUATE. NEC 215.2, 220, 408.30 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |
| | |