2018-03-13 11:05:10CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. WRONG CODE SPECIFIED FOR DESIGN. THE PROVISIONS OF
 THE FLORIDA BUILDING CODE, RESIDENTIAL SHALL APPLY TO
 THE CONSTRUCTION, ALTERATION, MOVEMENT, ENLARGEMENT,
 REPLACEMENT, REPAIR, EQUIPMENT, USE AND OCCUPANCY,
 LOCATION, REMOVAL AND DEMOLITION OF DETACHED ONE- AND
 TWO-FAMILY DWELLINGS AND TOWNHOUSES NOT MORE THAN THREE
 STORIES ABOVE GRADE PLANE IN HEIGHT WITH A SEPARATE
 MEANS OF EGRESS AND THEIR ACCESSORY STRUCTURES NOT MORE
 THAN THREE STORIES ABOVE GRADE PLANE IN HEIGHT. PROVIDE
 CORRECTION. FBC RE R101.2
 2. NOTE STATES THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT
 APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE
 CORRECTION. NEC 406.12; FBC RE E4002.14
 3. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4
 4. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC 210.8(D)
 5. PROVIDE AFCI PROTECTION PER CODE: ?BRANCH CIRCUITS
 THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE
 OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS, DINING
 ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED.? PROVIDE CORRECTION. NEC
 210.12
 6. PROVIDE NOTE TO COMPLY WITH CODE FOR LIGHTING IN
 CLOSETS: "LIGHTING WITH OPEN OR PARTIALLY ENCLOSED
 LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT
 BE PERMITTED IN CLOTHES CLOSETS". NEC 410.16
 7. WILL THERE BE ANY ADDITIONAL LOADS ADDED, NEW
 EQUIPMENT? IF SO, PROVIDE LOAD CALCULATION, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746