Plan Review Notes
Plan Review Notes For Permit 18020994
Permit Number 18020994
Review Stop E
Sequence Number 1
Notes
Date Text
2018-02-27 13:02:55FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
  
 RISER DIAGRAM FROM METER CAN TO DISCONNECT WIRE TO
 SMALL 350 KCMIL AL ONLY GOOD FOR 250A, CANNOT BE FUSED
 AT 300A 240.4(B)