Plan Review Notes
Plan Review Notes For Permit 18020950
Permit Number 18020950
Review Stop M
Sequence Number 1
Notes
Date Text
2018-03-05 12:42:021ST REVIEW FBC-2014 MECHANICAL
 REVISION #18020950
 MASTER #17060275
 3/5/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IN ORDER TO HELP EXPEDITE THE REVIEW PLEASE PROVIDE
 A NARRATIVE FROM THE DESIGN PROFESSIONAL THAT ITEMIZES
 AND EXPALINS WHAT CHANGES ARE VEING MADE TO THE
 APPROVED DRAWINGS.
  
 2) SHEET M1.2 : CU-2 MUST BE INSTALLED A MINIMUM OF 8'
 ABOVE THE FINISHED FLOOR OF THE PARKING GARAGE UNLESS
 PROTECTED FROM MOTOR VEHICLE IMPACT- SECTION 404.6.
  
 3) M0.2: CHANGES HAVBE BEEN MADE TO THE AC SYSTEMS THAT
 REQUIRE REVISED AC AND ENERGY CALCULATIONS. PLEASE
 PROVIDE THE REVIED CALCULATIONS.
  
 THE MECHANICAL REVIEW IS STOPPED AT THIS TIME PENDING
 RESUBMITTAL OF CORRECTED PLANS, REVISED CALCULATIONS,
 AND THE REQUESTED REVISION NARRATIVE,
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  