Plan Review Notes
Plan Review Notes For Permit 18020949
Permit Number 18020949
Review Stop M
Sequence Number 3
Notes
Date Text
2018-04-13 16:18:443RD REVIEW FBC-2017 MECHANICAL
 PERMIT #18020949
 4/13/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE DUPLICATE COPIES OF THE AC PLANS- ONLY ONE
 PLAN SET WAS SUBMITED- SECTION 107.2.1 WPB AMENDMENTS
 TO THE FBC.
  
 2) PROVIDE THE MAKES AND MODEL NUMBERS OF THE AC
 SYSTEMS ON THE PLAN. SECTION 107.2.1.
  
 3 ) THE CONTRACTOR SHALL PROVIDE HIS SIGNATURE ON THE
 PLANS. ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN- SECTION 107.2.1
 FBC. WPB AMENDMENTS TO THE FBC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  