| Plan Review Notes For Permit 18020949 |
| Permit Number |
18020949 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2018-04-13 16:18:44 | 3RD REVIEW FBC-2017 MECHANICAL | | | PERMIT #18020949 | | | 4/13/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE DUPLICATE COPIES OF THE AC PLANS- ONLY ONE | | | PLAN SET WAS SUBMITED- SECTION 107.2.1 WPB AMENDMENTS | | | TO THE FBC. | | | | | | 2) PROVIDE THE MAKES AND MODEL NUMBERS OF THE AC | | | SYSTEMS ON THE PLAN. SECTION 107.2.1. | | | | | | 3 ) THE CONTRACTOR SHALL PROVIDE HIS SIGNATURE ON THE | | | PLANS. ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN- SECTION 107.2.1 | | | FBC. WPB AMENDMENTS TO THE FBC. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|