Plan Review Notes
Plan Review Notes For Permit 18020949
Permit Number 18020949
Review Stop M
Sequence Number 2
Notes
Date Text
2018-03-15 14:05:242ND REVIEW FBC-2017 RESIDENTIAL MECHANICAL
 PERMIT #18020949
 3/15/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) AS PREVIOUSLY NOTED IN THE 1ST REVIEW, THE RETURN
 TRANSFER GRILLS IN THE BEDROOMS ARE UNDERSIDED. PLEASE
 ENLARGE THE GRILLS IN ACCORDANCE WITH SECTION M1602.3.
  
 2) THE PALM BEACH COUNTY PROPERTY APPRAISORS REPORT
 INDICATES THE RESIDENCE HAS HEATING AND AIR
 CONDITIONING, HOWEVER ACCORDING TO THE CONTRACTOR OF
 RECORD, THERE ARE NO EXISTING SYSTEMS. THE CONTRACTOR
 SHALL PROVIDE AC COOLING AND HEATING CALCULATIONS TO
 VERIFY SYSTEMS SELECTED ARE PROPERLY SIZED- M1401.3
  
 3) AN ELECTRICAL PLAN AND A PERMIT APPLICATION MUST BE
 SUBMITTED TO PROVIDE POWER TO THE AC SYSTREMS. SUBMIT A
 PLAN AND SUB-PERMIT APPLICATION UNDER THIS MECHANICAL
 PERMIT, OR SUBMIT A PLAN AND APPLICATION AS A SEPARATE
 PERMIT.
  
 4) THE SUBMITTAL FOR THE TIE-DOWN CLIP IS INCOMPLETE.
 PROVIDE THE COVER SHEET OF THE FLORIDA PRODUCT APPROVAL
 OR THE MIAMI-DADE NOA FOR THE CLIP, WHICHEVER IS
 APPLICABLE.
  
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  