| Plan Review Notes For Permit 18020949 |
| Permit Number |
18020949 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-03-15 14:05:24 | 2ND REVIEW FBC-2017 RESIDENTIAL MECHANICAL | | | PERMIT #18020949 | | | 3/15/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) AS PREVIOUSLY NOTED IN THE 1ST REVIEW, THE RETURN | | | TRANSFER GRILLS IN THE BEDROOMS ARE UNDERSIDED. PLEASE | | | ENLARGE THE GRILLS IN ACCORDANCE WITH SECTION M1602.3. | | | | | | 2) THE PALM BEACH COUNTY PROPERTY APPRAISORS REPORT | | | INDICATES THE RESIDENCE HAS HEATING AND AIR | | | CONDITIONING, HOWEVER ACCORDING TO THE CONTRACTOR OF | | | RECORD, THERE ARE NO EXISTING SYSTEMS. THE CONTRACTOR | | | SHALL PROVIDE AC COOLING AND HEATING CALCULATIONS TO | | | VERIFY SYSTEMS SELECTED ARE PROPERLY SIZED- M1401.3 | | | | | | 3) AN ELECTRICAL PLAN AND A PERMIT APPLICATION MUST BE | | | SUBMITTED TO PROVIDE POWER TO THE AC SYSTREMS. SUBMIT A | | | PLAN AND SUB-PERMIT APPLICATION UNDER THIS MECHANICAL | | | PERMIT, OR SUBMIT A PLAN AND APPLICATION AS A SEPARATE | | | PERMIT. | | | | | | 4) THE SUBMITTAL FOR THE TIE-DOWN CLIP IS INCOMPLETE. | | | PROVIDE THE COVER SHEET OF THE FLORIDA PRODUCT APPROVAL | | | OR THE MIAMI-DADE NOA FOR THE CLIP, WHICHEVER IS | | | APPLICABLE. | | | | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|