2018-02-27 13:23:011ST REVIEW FBC-2017 RESIDENTIAL MECHANICAL
 PERMIT #18020949
 2/27/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) CONTRACTOR'S SIGNATURE ON THE PLAN REQUIRED. ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN- SECTION 107.2.1 WEST PALM
 BEACH AMENDMENTS TO THE FBC.
  
 2) PROVIDE AC EQUIPMENT SCHEDULES ON THE PLANS.
  
 3) THE RETURN TRANSFERS ARE UNDERSIZED PER SECTION
 M1602.3. THE GRILLS SHALL BE SIZED 50 SQ. INCHES PER
 100 CFMS.
  
 4) PROVIDE ENGINEERING FOR TIE-DOWN OF THE NEW
 CONDENSERS- SECTION M1305.1.4.1
  