| 2018-02-27 10:52:49 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) SHEET 1 OF 4 - IS THIS AN OCCUPANCY CLASSIFICATION |
| | CHANGE? |
| | |
| | PLEASE PROVIDE THE EXISTING OCCUPANCY CLASSIFICATION |
| | AND PROPOSED ONE. |
| | |
| | |
| | |
| | |
| | 2) SHEET 1 OF 4 - THERE IS NO INDICATION OF COMPLIANCE |
| | OR REVIEW OF COMLAINCE WITH ANY FIRE PREVENTION CODE. |
| | |
| | THE PROPOSED PROJECT SHALL MEET THE REQUIREMNTS OF THE |
| | FLORIDA FIRE PREVENTION CODE, 2015 EDITION. |
| | |
| | PLEASE PROVIDE AN APPLICABLE NOTE OF COMPLAINACE AND |
| | REVIEW. |
| | |
| | |
| | |
| | |
| | 3) SHEET 1 OF 4 - THERE APPEARS TO BE ADJACENT |
| | OCCUPANCY WALL SEPARATION. |
| | |
| | PLEASE PROVIDE THE ADJACENT OCCUPANCIES AND THE |
| | REQUIRED FIRE RATING SEPARATION PER THE FFPC. |
| | |
| | |
| | |
| | |
| | 4) SHEET 1 OF 4 - THERE IS NO INDICATION OF A DOOR |
| | SCHEDULE. |
| | |
| | PLEASE PROVIDE A DOOR SCHEDULE INCLUDING LOCKS AND |
| | HARDWARE AND ENSURE IT MEETS THE REQUIREMENT OF THE |
| | FFPC INCLUDING MEANS OF EGRESS. |
| | |
| | |
| | |
| | |
| | |
| | 5) THERE IS NO SHEET 2 OF 4. |
| | |
| | PLEASE REVIEW AND PROVIDE OR ACCOUNT FOR. |
| | |
| | |
| | |
| | |
| | 5) SHEET 3 OF 4 - THERE IS NO INDICATION OF EXIT |
| | SIGNAGE. |
| | |
| | NFPA 101 CHAPTER 36, NEW MERCANTILE OCCUPANCIES |
| | 36.2.8 ILLUMINATION OF MEANS OF EGRESS. MEANS OF EGRESS |
| | SHALL |
| | BE ILLUMINATED IN ACCORDANCE WITH SECTION 7.8. |
| | |
| | 36.2.10 MARKING OF MEANS OF EGRESS. WHERE AN EXIT IS |
| | NOT |
| | IMMEDIATELY APPARENT FROM ALL PORTIONS OF THE SALES |
| | AREA, MEANS OF |
| | EGRESS SHALL HAVE SIGNS IN ACCORDANCE WITH SECTION |
| | 7.10. |
| | |
| | NFPA 101 CHAPTER 7, MEANS OF EGRESS |
| | |
| | 7.8 ILLUMINATION OF MEANS OF EGRESS. |
| | 7.8.1 GENERAL. |
| | 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE |
| | PROVIDED IN |
| | ACCORDANCE WITH SECTION 7.8 FOR EVERY BUILDING AND |
| | STRUCTURE WHERE |
| | REQUIRED IN CHAPTERS 11 THROUGH 43. FOR THE PURPOSES OF |
| | THIS |
| | REQUIREMENT, EXIT ACCESS SHALL INCLUDE ONLY DESIGNATED |
| | STAIRS, AISLES, |
| | CORRIDORS, RAMPS, ESCALATORS, AND PASSAGEWAYS LEADING |
| | TO AN EXIT. FOR THE |
| | PURPOSES OF THIS REQUIREMENT, EXIT DISCHARGE SHALL |
| | INCLUDE ONLY |
| | DESIGNATED STAIRS, AISLES, CORRIDORS, RAMPS, |
| | ESCALATORS, WALKWAYS, AND EXIT |
| | PASSAGEWAYS LEADING TO A PUBLIC WAY. |
| | 7.8.1.2 ILLUMINATION OF MEANS OF EGRESS SHALL BE |
| | CONTINUOUS DURING THE |
| | TIME THAT THE CONDITIONS OF OCCUPANCY REQUIRE THAT THE |
| | MEANS OF EGRESS |
| | BE AVAILABLE FOR USE, UNLESS OTHERWISE PROVIDED IN |
| | 7.8.1.2.2. |
| | 7.10.1.2 EXITS. |
| | 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS |
| | THAT OBVIOUSLY |
| | AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED |
| | BY AN APPROVED |
| | SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT |
| | ACCESS. |
| | 7.10.1.2.2* HORIZONTAL COMPONENTS OF THE EGRESS PATH |
| | WITHIN AN EXIT |
| | ENCLOSURE SHALL BE MARKED BY APPROVED EXIT OR |
| | DIRECTIONAL EXIT SIGNS |
| | WHERE THE CONTINUATION OF THE EGRESS PATH IS NOT |
| | OBVIOUS. |
| | 7.10.1.3 EXIT DOOR TACTILE SIGNAGE. TACTILE SIGNAGE |
| | SHALL BE |
| | PROVIDED TO MEET ALL OF THE FOLLOWING CRITERIA, UNLESS |
| | OTHERWISE |
| | PROVIDED IN 7.10.1.4: |
| | (1) TACTILE SIGNAGE SHALL BE LOCATED AT EACH EXIT DOOR |
| | REQUIRING AN |
| | EXIT SIGN. |
| | (2) TACTILE SIGNAGE SHALL READ AS FOLLOWS: EXIT. |
| | (3) TACTILE SIGNAGE SHALL COMPLY WITH ICC/ANSI A117.1, |
| | AMERICAN |
| | NATIONAL STANDARD FOR ACCESSIBLE AND USABLE BUILDINGS |
| | AND |
| | FACILITIES. |
| | |
| | |
| | PLEASE PROVIDE PER FFFC, NFPA 101, CHAPTER 36 & 7 MEANS |
| | OF EGRESS. |
| | |
| | |
| | |
| | |
| | 6) THERE ARE NO INCIATIONS OF ANY EXISTING OR PROPOSED |
| | FIRE SPRINKLER OR FIRE ALARM SYSTEMS. |
| | |
| | PLEASE REVIEW AND PROVIDE AND APPLICABLE NOTE ON SHEET |
| | 1 OF 4. |
| | |
| | |
| | |
| | |
| | 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |
| | |