| Plan Review Notes For Permit 18020938 |
| Permit Number |
18020938 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-03-01 06:56:11 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PLANS ARE REQUIRED TO BE DESIGNED AND SIGNED AND | | | SEALED BY A LICENSED ENGINEER OR ARCHITECT. PLANS | | | FURNISHED BY AN INTERIOR DESIGNER ARE NOT ACCEPTABLE. | | | PROVIDE CORRECTION. FS 471.003(2)(H); 471.025; FBC | | | 107.2.1, 107.3.5 | | | 2. A FULL REVIEW IS NOT POSSIBLE AT THIS TIME DUE TO A | | | SUBSTANTIAL LACK OF INFORMATION. FBC 107.2.1 | | | 3. VALUE STATED ON PERMIT APPLICAITON APPEARS LOW. | | | PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND VALUE OF | | | WORK, TO INCLUDE ALL MATERIALS AND LABOR. FBC 109.3 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | | | | |
|