| 2018-02-28 10:55:51 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 18020938 |
| | ADD: 1401 CLARE AVENUE, SUITE : |
| | CONT: TIM GIVENS BUILDING & REMODELING |
| | TEL: 561-533-5828 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. FEB. 28/ 2018 |
| | ACTION: DENIED |
| | |
| | 1) THE SUBMITTED PLANS NOR THE PERMIT APPLICATION |
| | PROVIDE WHICH SUITE WORK IS TO BE COMPLETED UNDER THIS |
| | PERMIT. |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED. |
| | |
| | 2017 FBC-B 501.2 ADDRESS IDENTIFICATION. NEW AND |
| | EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED |
| | ADDRESS IDENTIFICATION. |
| | |
| | 2) THE SUBMITTED PLANS STATE THERE ARE 4 SHEETS 1 OF 4 |
| | FOR EXAMPLE, MISSING SHEET 2 OF 4 IN ALL THREE SETS. |
| | 107.2.1.3 ADDITIONAL INFORMATION. |
| | |
| | 3) PLEASE BE AWARE UNDER PERMIT 16090638/ REVISION |
| | 17011285 (AS BUILT PLANS) THIS UNIT WAS CLASSIFIED AS A |
| | BUSINESS OCCUPANCY WITH AN EXISTING HANDICAPPED |
| | RESTROOM AND A COUNTER WITH BREAKROOM SINK. THE |
| | SUBMITTED PLANS DO NOT SHOW THIS ARRANGEMENT NOR DO |
| | THEY SHOW A DEMOLITION PLAN WITH THE REMOVAL OF THESE |
| | SYSTEMS NOR IS THERE A DEMOLITION PERMIT FOR THIS UNIT |
| | SHOWING THE REMOVAL OF THESE ELEMENTS. |
| | FURTHER MORE ADDITIONAL WORK HAS OCCURRED MAKING A TENT |
| | EFFECT(POLES, CANVAS AND ELECTRICAL FIXTURES AND HUNG |
| | LIGHTING), AT THE DOUBLE DOOR ENTRY AND CANVAS ON |
| | WALLS. 4 X THE FEE WILL BE CHARGED AGAINST THIS PERMIT |
| | FOR WORK COMPLETED WITHOUT THE BENEFIT OF A PERMIT. |
| | |
| | 109.4 WORK COMMENCING BEFORE PERMIT ISSUANCE. ANY |
| | PERSON WHO COMMENCES ANY WORK ON A BUILDING, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL OR PLUMBING SYSTEM BEFORE |
| | OBTAINING THE BUILDING OFFICIAL?S APPROVAL OR THE |
| | NECESSARY PERMITS SHALL BE SUBJECT TO A PENALTY FEE IN |
| | ADDITION TO THE REQUIRED PERMIT FEES, AS SET IN |
| | APPROVED SCHEDULE OF FEES. |
| | |
| | 4) SINCE UNDER THE AS BUILT REVISION 17101285 THE |
| | TENANT SPACE IN QUESTION WAS NO LONGER A VANILLA BOX AN |
| | OCCUPANCY WAS ASSIGNED (BUSINESS) AND UNISEX RESTROOM |
| | WAS SHOWN ON THE PLANS. THIS IS NOW CONSIDERED A CHANGE |
| | OF OCCUPANCY AND WILL NEED TO COMPLY WITH THE 2017 |
| | EXISTING BUILDING CODE SECTION |
| | 1001.2.2.1 PARTIAL CHANGE OF OCCUPANCY. WHERE THE |
| | OCCUPANCY CLASSIFICATION OR GROUP OF A PORTION OF AN |
| | EXISTING BUILDING IS CHANGED, SECTION 1012 SHALL APPLY. |
| | |
| | THE PLANS ARE NOT DISCLOSING THE MINIMUM INFORMATION |
| | FOR COMMERCIAL BUILDING PLAN REVIEW FOR BUILDINGS. |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS |
| | SHALL BE DETERMINED. |
| | MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE |
| | TABLES 504.3, TABLE 504.4 & TABLE 506.2). |
| | OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| | OCCUPANCY LOAD |
| | GROSS |
| | FIRE SPRINKLERED OR NOT? |
| | IS FIRE SPRINKLERS REQUIRED? |
| | NET |
| | MEANS OF EGRESS |
| | EXIT ACCESS |
| | EXIT |
| | EXIT DISCHARGE |
| | STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION |
| | DOORS |
| | ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE FOLLOWING: |
| | SITE REQUIREMENTS |
| | ACCESSIBLE ROUTE |
| | VERTICAL ACCESSIBILITY |
| | TOILET AND BATHING FACILITIES |
| | DRINKING FOUNTAINS |
| | INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING: |
| | INTERIOR FINISHES/ WALLS AND CEILING (FLAME |
| | SPREAD/SMOKE DEVELOPMENT) |
| | LIGHT AND VENTILATION |
| | SANITATION MISSING RESTROOMS. |
| | SPECIAL SYSTEMS: (VERTICAL ACCESSIBILITY) |
| | ELEVATORS |
| | ESCALATORS |
| | LIFTS |
| | |
| | 5) THE SUBMITTED PLAN WAS CREATED BY AN INTERIOR |
| | DECORATOR MARGARET B KAYWELL ID 0005475THE SCOPE OF THE |
| | PROJECT FAR EXCEEDS THE LIMITATIONS OF THIS LICENSE. |
| | |
| | 5A) MISSING REQUIRED STATEMENT ON THE PLANS: 481.2131. |
| | A REGISTERED INTERIOR DESIGNER SHALL CONTAIN A |
| | STATEMENT THAT THE DOCUMENT IS NOT AN ARCHITECTURAL OR |
| | ENGINEERING STUDY, DRAWING, SPECIFICATION, OR DESIGN |
| | AND IS NOT TO BE USED FOR CONSTRUCTION OF ANY |
| | LOAD-BEARING COLUMNS, LOAD-BEARING FRAMING OR WALLS OF |
| | STRUCTURES, OR ISSUANCE OF ANY BUILDING PERMIT, EXCEPT |
| | AS OTHERWISE PROVIDED BY LAW. |
| | |
| | 5B) FLORIDA STATUTE 481.2131(1). UNDER THE DEFINITIONS |
| | 481.203 FOR INTERIOR DESIGN(8) ?INTERIOR DESIGN? |
| | SPECIFICALLY EXCLUDES THE DESIGN OF OR THE |
| | RESPONSIBILITY FOR ARCHITECTURAL AND ENGINEERING WORK, |
| | EXCEPT FOR SPECIFICATION OF FIXTURES AND THEIR LOCATION |
| | WITHIN INTERIOR SPACES. AS USED IN THIS SUBSECTION, |
| | ?ARCHITECTURAL AND ENGINEERING INTERIOR CONSTRUCTION |
| | RELATING TO THE BUILDING SYSTEMS? INCLUDES, BUT IS NOT |
| | LIMITED TO, CONSTRUCTION OF STRUCTURAL, MECHANICAL, |
| | PLUMBING, HEATING, AIR-CONDITIONING, VENTILATING, |
| | ELECTRICAL, OR VERTICAL TRANSPORTATION SYSTEMS, OR |
| | CONSTRUCTION WHICH MATERIALLY AFFECTS LIFESAFETY |
| | SYSTEMS PERTAINING TO FIRESAFETY PROTECTION SUCH AS |
| | FIRE-RATED SEPARATIONS BETWEEN INTERIOR SPACES, |
| | FIRE-RATED VERTICAL SHAFTS IN MULTISTORY STRUCTURES, |
| | FIRE-RATED PROTECTION OF STRUCTURAL ELEMENTS, SMOKE |
| | EVACUATION AND COMPARTMENTALIZATION, EMERGENCY INGRESS |
| | OR EGRESS SYSTEMS, AND EMERGENCY ALARM SYSTEMS. |
| | UNDER COMMENT # 4 THESE ARE THE AREAS NOT SHOWN ON THE |
| | PLAN, AND UNDER THE INTERIOR DESIGN LICENSE NOT IN THE |
| | SCOPE OF THEIR LICENSURE. |
| | |
| | 6) PLEASE PROVIDE A LIFE SAFETY PLAN FOR THIS TENANT |
| | SPACE SHOWING BOTH A MEANS OF EGRESS AS WELL AS THE |
| | ACCESSIBLE MEANS OF EGRESS TO THE PUBLIC WAY. PLEASE |
| | INCLUDE THE ADJACENT TENANT SPACE WHERE YOU HAVE TO GO |
| | THROUGH THE ADJACENT TENANT SPACE TO AN EXIT. PROVIDE |
| | THE TYPE OF OCCUPANCIES ADJACENT TO THE MERCANTILE |
| | OCCUPANCY. PLEASE ALSO INCLUDE COMMON PATH OF TRAVEL |
| | AND EXIT ACCESS TRAVEL TO THE EXIT DISCHARGE. |
| | 2017 FBC-B TABLE 1006.2.1. PLEASE BE AWARE THAT FOR AN |
| | ACCESSIBLE MEANS OF EGRESS YOU ARE AT 79 FEET FROM THE |
| | FURTHEST POINT IN THE TENANT SPACE TO THE DOUBLE ENTRY |
| | DOORS. YOU STILL HAVE TO GO THROUGH A SECOND TENANT |
| | SPACE BEFORE YOU GET TO AN EXIT DISCHARGE. |
| | TABLE 1017.2 EXIT ACCESS TRAVEL DISTANCE. |
| | |
| | 7)2017 FBC-B 1016.2 EGRESS THROUGH INTERVENING SPACES. |
| | EGRESS THROUGH INTERVENING SPACES SHALL COMPLY WITH |
| | THIS SECTION. |
| | (2).EGRESS FROM A ROOM OR SPACE SHALL NOT PASS THROUGH |
| | ADJOINING OR INTERVENING ROOMS OR AREAS, EXCEPT WHERE |
| | SUCH ADJOINING ROOMS OR AREAS AND THE AREA SERVED ARE |
| | ACCESSORY TO ONE OR THE OTHER, ARE NOT A GROUP H |
| | OCCUPANCY AND PROVIDE A DISCERNIBLE PATH OF EGRESS |
| | TRAVEL TO AN EXIT. |
| | |
| | 8) PLEASE NOTE WITH THE CITY BUILDING INSPECTORS BEING |
| | AT THE SITE AT PICTURES WERE TAKEN OF A CANVAS TENT |
| | LIKE CEILING ASSEMBLY AND CANVAS ON THE TENANT WALLS |
| | PLEASE PROVIDE COMPLIANCE WITH TEXTILE WALL AND CEILING |
| | COVERINGS. |
| | |
| | 8A) 2017 FBC-B 803.5 TEXTILE WALL COVERINGS. WHERE USED |
| | AS INTERIOR WALL FINISH MATERIALS, TEXTILE WALL |
| | COVERINGS, INCLUDING MATERIALS HAVING WOVEN OR |
| | NONWOVEN, NAPPED, TUFTED, LOOPED OR SIMILAR SURFACE AND |
| | CARPET AND SIMILAR TEXTILE MATERIALS, SHALL BE TESTED |
| | IN THE MANNER INTENDED FOR USE, USING THE PRODUCT |
| | MOUNTING SYSTEM, INCLUDING ADHESIVE, AND SHALL COMPLY |
| | WITH THE REQUIREMENTS OF SECTION 803.1.2, 803.1.3 OR |
| | 803.1.4. |
| | |
| | 8B) 2017 FBC-B 803.6 TEXTILE CEILING COVERINGS. WHERE |
| | USED AS INTERIOR CEILING FINISH MATERIALS, TEXTILE |
| | CEILING COVERINGS, INCLUDING MATERIALS HAVING WOVEN OR |
| | NONWOVEN, NAPPED, TUFTED, LOOPED OR SIMILAR SURFACE AND |
| | CARPET AND SIMILAR TEXTILE MATERIALS, SHALL BE TESTED |
| | IN THE MANNER INTENDED FOR USE, USING THE PRODUCT |
| | MOUNTING SYSTEM, INCLUDING ADHESIVE, AND SHALL COMPLY |
| | WITH THE REQUIREMENTS OF SECTION 803.1.2 OR 803.1.4. |
| | |
| | 8C) SHOW COMPLIANCE WITH FBC-B 803.11 INTERIOR FINISH |
| | REQUIREMENTS BASED ON GROUP. |
| | |
| | 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF |
| | PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR |
| | REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE |
| | OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST |
| | PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE |
| | STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL |
| | (561)233-5025 FOR MORE INFORMATION. |
| | |
| | 10) A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN |
| | SINCE THERE WAS A GREAT DEFICIENCY IN PLANS AND |
| | REQUIRED DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE |
| | THERE MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW |
| | PLANS AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |