2018-03-17 06:33:511ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHOW LOCATION AND SIZE OF WATER SERVICE. PER WPB
 AMEND TO FBC 107.2.1
  
 2. BACKFLOW REQUIRED ON WATER SERVICE PLACE NOTE ON
 PLAN SEPARATE PERMIT REQUIRED FOR BACKFLOW. PER WPB
 UTILITIES DEPT CROSS CONNECTION MANUAL
  
 3. SHOW SIZE AND LOCATION OF HOLDING TANK IF OVER 300
 GAL A PERMIT FROM FLORIDA DEPARTMENT OF HEALTH IS
 REQUIRED. PER WPB AMEND TO FBC 107.2.1
  
 4. PROVIDE CONTRACT FOR HOLDING TANK PUMP OUT. PER WPB
 AMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  